Overview
This article explains the different types of cables used for connecting the Control Unit (CU-4E/CU-4D) with the Gen 5/Gen 6 family of sensors. For the list of all Gen 5/Gen 6 cables, refer to the Cables (CBL-xx-xx-xx) - Spec Sheet .
The Control Units (CU-4) applies to the following models:
- Fixture Mount Control Unit for 0-10V drivers: CU-4E-FMH,
- Nipple Mount External/Internal Control Unit: CU-4E-NME/NMI, for North America only
The Control Units (CU-4D) applies to the following models:
- Fixture Mount Control Unit for DALI drivers: CU-4D-FM, for use in the EU only.
The following sections are categorized based on the type of Gen 5 sensor connected to the Control Unit (CU-4E/CU-4D).
Overview: Gen 5/Gen 6 Sensors Cabling Matrix
The Sensor Cabling Matrix table provides an overview of the cables needed to connect a Gen 5 sensor to the Control Unit. The table is categorized based on the type of Gen 5 sensor and Control Unit model.
The maximum cable length between an Enlighted SU-5 sensor (SU-5E or SU-5S) and a CU-4E/CU-4D control unit can be up to 300' of CAT3 or better (CAT5, 5E, 6E) cable. Multiple cables from different sensors going to different CUs can share the same raceway or cable tray without signal degradation or cross-talk. Maintain the separation of circuits from class 1 wiring per the requirements of the AHJ.
Note: All Enlighted cables are plenum-rated as indicated by the CMP (Communications Multipurpose Plenum), 600 VAC, #24 AWG CAT 3 cables, and UL numbers are indicated on the cable.

Notes:
- All Ruggedized sensors (-xRx) have integrated 20" cable with connector (RJ12 or RJ45). Note the required cable extensions in the table.
- Any Gen 5, 2-wire sensor can be connected to function as a fixtureless sensor. For details, refer to 2-wire Fixtureless Sensors.
- All IoT, Connected Lighting (CL), and Independent Lighting (IL) product codes for Micro sensor (SU-5E), High Bay, Ruggedized sensors (SU-5S) are covered in the appropriate SU-5E/5S sensor column.
Control Unit (CU-4E/CU-4D) with Micro Sensor (SU-5E)
The Control Unit (CU-4E) applies to the following models. The DALI Fixture Mount (CU-4D-FM) is for use in the EU only.
1. CU-4E-FMH and CU-4D-FM with Micro Sensor
Use any of the following cables for connecting the Control Unit with the Micro Sensor (SU-5E).
- 30-inch sensor cable, (CBL-5E-CU4-30N): 12-02290-02
- 7-foot sensor cable, (CBL-5E-CU4-7F): 12-02285-02
- 15-foot sensor cable, (CBL-5E-CU4-15F): 12-03267-01
- 25-foot sensor cable, (CBL-5E-CU4-25F): 12-03268-01
- 50-foot sensor cable, (CBL-5E-CU4-50F): 12-03248-01
- 75-foot sensor cable, (CBL-5E-CU4-75F): 12-03269-01
- 100-foot sensor cable, (CBL-5E-CU4-100F): 12-03270-01
The above cables have an 8-pin Molex connector on one end that connects to a sensor and an RJ-45 connector that connects to the CU-4E/CU-4D on the other end. The cables, along with their terminal connectors, are shown below.

30-inch Sensor Cable

7-foot Sensor Cable

15/25/75/100-foot Sensor Cable
Refer to the line diagram SU-5 and CU-4E with one or more 0-10V Drivers (02693-05) for details.

Refer to the line diagram SU-5 with CU-4D with one or more DALI Drivers (02945-02) for details.

2. CU-4E-NMI with Micro Sensor
You will need the following cable and connector for the Nipple Mount Internal (CU-4E-NMI) with the Micro sensor.
- 12-inch sensor cable, (CBL-5E-CU4-12N): 12-02289-02.
- Female RJ45 coupler, (CPL-RJ45): 27-00379-01.
This cable has an 8-pin Molex connector on one end that connects to the sensor and an RJ-45 connector on the other end to the CU-4E.

12-inch Sensor Cable

Female RJ-45 Coupler (CPL-RJ45)
3. CU-4E-NME with Micro Sensor
The Nipple Mount External (CU-4E-NME) with the Micro sensor requires the following cable:
- 12-inch sensor cable, (CBL-5E-CU4-12N): 12-02289-02.
To extend cable length, connect CPL-RJ45 (or standard CAT5e coupler) to RJ-45 end of the cable and connect standard RJ45-to-RJ45 straight-through cable of the desired length between the CPL-RJ45 coupler and CU-4E. It can be purchased readily.
Refer to the line diagram SU-5 and CU-4E (NME) with one or more 0-10V Drivers (03155-01) for details.

4. CU-4A-NME with Micro Sensor
The Nipple Mount External (CU-4A-NME-16A) with the Micro sensor requires the following cable:
- 12-inch sensor cable, (CBL-5E-CU4-12N): 12-02289-02.
To extend cable length, connect CPL-RJ45 (or standard CAT5e coupler) to RJ-45 end of the cable and connect standard RJ45-to-RJ45 straight-through cable of the desired length between the CPL-RJ45 coupler and CU-4E. It can be purchased readily.
Refer to the line diagram SU-5E/SU-6E Sensor and CU-4A-FME-16A Control Unit with Single Channel 0-10V Driver for details.

Control Unit (CU-4E/CU-4D) with High Bay Sensor (SU-5S-H)
To connect the Control Unit (CU-4E-FMH, CU-4D-FM, CU-4E-NME/NMI) with the High Bay Sensor (SU-5S), you will need the following cable.
- 7-foot RJ45 cable, (CBL-RJ45-RJ45-7F): 12-02627-02.
- Optional Female RJ45 coupler (CPL-RJ45): 27-00379-01 to extend the cable length.
This cable has an RJ-45 connector connected to the CU-4E and an RJ-45 connector connected to the sensor on the other end.

7-foot RJ45 Cable
Standard RJ45-RJ45 patch cables of the desired length can be used instead of the above cable. However, please note that a short-body RJ45 connector is recommended at the sensor-end to allow for a shorter cable bend radius if the sensor is flush-mounted against a flat surface. The maximum cable length between an Enlighted SU-5 sensor (SU-5E or SU-5S) and CU-4E/CU-4D control unit can be up to 300' of CAT3 or better (CAT5, 5E, 6E) cable.
Refer to the line diagram Gen 5 Sensor with Control Unit: SU-5 and CU-4E with one or more 0-10V Drivers (02693-05) for details.

Refer to the line diagram SU-5 with CU-4D with one or more DALI Drivers (02945-02) for details.

Control Unit (CU-4E/CU-4D) with Ruggedized Sensor (SU-5S-xRx)
The following cables are needed to connect the Control Unit (CU-4E-FMH, CU-4D-FM, CU-4E-NME/NMI) with the Ruggedized sensor (SU-5S-xRx). However, no cable is required if the Ruggedized sensor's 20-inch sensor cable length is sufficient to connect.
- 7-foot RJ45 cable, (CBL-RJ45-RJ45-7F): 12-02627-02.
- Optional Female RJ45 coupler (CPL-RJ45): 27-00379-01 to extend the cable length.
This cable has an RJ-45 connector connected to the CU-4E and an RJ-45 connector that connects to the sensor on the other end. The cable, along with the terminal connectors, is shown below.

7-foot RJ45 Cable
To extend cable length, connect CPL-RJ45 (or standard CAT5e coupler) to RJ-45 end of the above cable and connect standard RJ45-to-RJ45 straight-through cable of the desired length between CPL-RJ45 coupler and CU-4E. It can be purchased readily. The maximum cable length between an Enlighted SU-5 sensor (SU-5E or SU-5S) and CU-4E control unit can be up to 300' of CAT3 or better (CAT5, 5E, 6E) cable.
Control Unit (CU-4E) with Ruggedized Sensor (SU-5S-xRx)

Control Unit (CU-4D) with Ruggedized Sensor (SU-5S-xRx)
Gen 5 Sensors 8-Pin Assignments
Gen 5 sensors have the following pin assignments:
Pin | Description |
Pin 1 | Not Connected |
Pin 2 | Not Connected |
Pin 3 | Dimming Channel 2 |
Pin 4 | GND |
Pin 5 | VDD |
Pin 6 | Dimming Channel 1 |
Pin 7 | RX Data |
Pin 8 | TX Data |
Cable Assembly

7-foot RJ45 Cable Assembly

Female RJ45 Coupler, (CPL-RJ45), 27-00379-01

Line Diagrams
Refer to the following line diagrams to understand the connection between the Gen 5 sensor and Control Unit (CU-4E/CU-4D). The Control Unit (CU-4E) applies to the models: CU-4E-FMH, CU-4D-FM, CU-4E-NME/NMI.