For Canadian installations where the mains voltage is frequently 347 VAC, which is beyond the limits of the Enlighted Control Unit (CU-4E), Enlighted suggests the following 347 VAC drivers that are compatible with the 2-wire SU-5 sensors when used in conjunction with an XSR Bridge. The following list of DALI drivers and 0-10V drivers can be used directly with the Enlighted 2-wire sensors with an XSR Bridge.
DALI Drivers with Built-in Power Supply Unit and Power Metering Function
When you select one of the following listed drivers, the driver provides sensor powering and supports the DALI Power Metering function directly.
Manufacturer | Model Number | Certifications | Power Rating (W) |
Input Voltage Range
(VAC/DC)
|
Output Current
(mA)
|
Output Voltage Range
(VDC)
| Dimming Type |
PSU in the Driver
(Yes/No)
|
Power metering function
(Yes/No)
|
Philips/Signify | XJ180C090V285VSF2M | UL ETL CSA D4i | 180 | 277 - 480 | 100 - 900 | 100 - 285 | DALI Log 10 - 100% and DALI Linear 10 - 100% | Yes | Yes |
Philips/Signify | XJ180C125V210VSF2M | UL ETL CSA D4i | 180 | 277 - 480 | 100 - 1250 | 70 - 210 | DALI Log 10 - 100% and DALI Linear 10 - 100% | Yes | Yes |
Philips/Signify | XJ180C180V144VSF2M | UL ETL CSA D4i | 180 | 277 - 480 | 100 - 1800 | 50 - 144 | DALI Log 10 - 100% and DALI Linear 10 - 100% | Yes | Yes |
DALI Drivers without Power Supply Unit or Power Metering Function
When you select one of the following listed drivers, an External DALI PSU is required. To set up Soft Metering, the fixture manufacturer must provide the power consumption vs dimming setting.
Manufacturer | Model Number | Certifications | Power Rating (W) |
Input Voltage Range
(VAC/DC)
|
Output Current
(mA)
|
Output Voltage Range
(VDC)
| Dimming Type |
PSU in the Driver
(Yes/No)
|
Power metering function
(Yes/No)
|
ULT | D700C30347D-C | UL | 30 | 347 VAC | 700 | 15 - 44 | DALI 1% | No | No |
ULT | D10CC30347D-C | UL | 30 | 347 VAC | 1050 | 15 - 44 | DALI 1% | No | No |
ULT | D10CC55347D-C | UL | 55 | 347 VAC | 1050 | 11 - 29 | DALI 1% | No | No |
ULT | D15CC55347D-C | UL | 55 | 347 VAC | 1500 | 15 - 37 | DALI 1% | No | No |
ULT | D21CC80347D-D | UL | 80 | 347 VAC | 2100 | 11 - 38 | DALI 1% | No | No |
ULT | D10CC55347D-K/KS | UL | 55 | 347 VAC | 1050 | 11 - 29 | DALI 1% | No | No |
ULT | D15CC55347D-K/KS | UL | 55 | 347 VAC | 1500 | 15 - 37 | DALI 1% | No | No |
| | | | | | | | | |
0-10V Profile 0 Dimming LED Drivers
The list of 0-10V drivers is available at different power levels from 20 to 95 watts to meet various luminaire size requirements. You can use multiple drivers with a single 2-wire sensor and the XSR-Bridge.
Manufacturer | Model Number | Certifications | Power Rating (W) | Input Voltage Range (VAC) | Output Current (mA) | Output Voltage Range (VDC) | Dimming Type |
Osram | OTi 30/347/1A0 DIM L AUX | UL | 30 | 347 | 350 - 1050 | 10 - 55 | 0 - 10V 10% |
Osram | OTi 48/347/2A0 DIM L AUX | UL | 48 | 347 | 700 - 2000 | 10 - 55 | 0 - 10V 10% |
Osram | OTi 48/347/2A0 DIM-1 L AUX | UL | 48 | 347 | 700 - 2000 | 10 - 55 | 0 - 10V 1% |
Osram | OTi 50/347/1A4 DIM L AUX | UL | 50 | 347 | 400 - 1400 | 10 - 55 | 0 - 10V 10% |
Osram | OTi 85/347-480/2A3 DIM-1LHB AUX | UL | 85 | 347 - 480 | 700 -2300 | 10 - 55 | 0 - 10V 10% |
Osram | OTi 85/347-480/2A3 DIM-1 L AUX | UL | 85 | 347-480 | 700 - 2300 | 10 - 55 | 0 - 10V 10% |
Osram | OTi 95W/UNV/2750C/2DIM+/P6/AUX | UL | 95 | 347-480 | 700 - 2750 | 15 - 54 | 0 - 10V 1% |
| | | | | | | |
This solution with the XSR bridge is only for 2-wire sensors; the 2-wire sensor connects to the XSR bridge. See the line diagram SU-5 (2-wire) with XSR Bridge and (347v) 0-10v Driver (03066-02), which is the most preferred solution.
An alternative method, when energy metering is not required, uses a 347 VAC Profile 0 driver with an 8-pin sensor and adapter cable. In this case, the sensor is powered from the Auxiliary DC supply of the driver. Refer to the following line diagrams: