Salesforce

Canadian Wiring 347 VAC Solutions

« Go Back
Information
Canadian Wiring 347 VAC Solutions
ka03o000001DtcXAAS
Article Details

For Canadian installations where the mains voltage is frequently 347 VAC, which is beyond the limits of the Enlighted Control Unit (CU-4E), Enlighted suggests the following 347 VAC drivers that are compatible with the 2-wire SU-5 sensors when used in conjunction with an XSR Bridge. The following list of DALI drivers and 0-10V drivers can be used directly with the Enlighted 2-wire sensors with an XSR Bridge.

DALI Drivers with Built-in Power Supply Unit and Power Metering Function

When you select one of the following listed drivers, the driver provides sensor powering and supports the DALI Power Metering function directly.

ManufacturerModel NumberCertifications      Power Rating (W)

Input Voltage Range

(VAC/DC) 

Output Current

(mA)  

Output Voltage Range

(VDC)

Dimming Type                                                              

PSU in the Driver

(Yes/No)

Power metering function

(Yes/No) 

Philips/SignifyXJ180C090V285VSF2MUL ETL CSA D4i180277 - 480100 - 900100 - 285DALI Log 10 - 100% and DALI Linear 10 - 100%YesYes
Philips/SignifyXJ180C125V210VSF2MUL ETL CSA D4i180277 - 480100 - 125070 - 210DALI Log 10 - 100% and DALI Linear 10 - 100%YesYes
Philips/SignifyXJ180C180V144VSF2MUL ETL CSA D4i180277 - 480100 - 180050 - 144DALI Log 10 - 100% and DALI Linear 10 - 100%YesYes

DALI Drivers without Power Supply Unit or Power Metering Function

When you select one of the following listed drivers, an External DALI PSU is required.  To set up Soft Metering, the fixture manufacturer must provide the power consumption vs dimming setting.

ManufacturerModel Number        CertificationsPower Rating (W)

Input Voltage Range

(VAC/DC)

Output Current

(mA)                            

Output Voltage Range

(VDC)

Dimming Type

PSU in the Driver

(Yes/No)

Power metering function

(Yes/No)

ULTD700C30347D-C UL30347 VAC70015 - 44DALI 1%NoNo
ULTD10CC30347D-C UL30347 VAC105015 - 44DALI 1%NoNo
ULTD10CC55347D-C UL55347 VAC105011 - 29DALI 1%NoNo
ULTD15CC55347D-C UL55347 VAC150015 - 37DALI 1%NoNo
ULTD21CC80347D-DUL80347 VAC210011 - 38DALI 1%NoNo
ULTD10CC55347D-K/KSUL55347 VAC105011 - 29DALI 1%NoNo
ULTD15CC55347D-K/KSUL55347 VAC150015 - 37DALI 1%NoNo
          

0-10V Profile 0 Dimming LED Drivers

The list of 0-10V drivers is available at different power levels from 20 to 95 watts to meet various luminaire size requirements. You can use multiple drivers with a single 2-wire sensor and the XSR-Bridge.

Manufacturer            Model Number                                                 CertificationsPower Rating (W)Input Voltage Range (VAC)Output Current (mA)                               Output Voltage Range (VDC)              Dimming Type
OsramOTi 30/347/1A0 DIM L AUXUL30347350 - 105010 - 550 - 10V 10%
OsramOTi 48/347/2A0 DIM L AUXUL48347700 - 200010 - 550 - 10V 10%
OsramOTi 48/347/2A0 DIM-1 L AUXUL48347700 - 200010 - 550 - 10V 1%
OsramOTi 50/347/1A4 DIM L AUXUL50347400 - 140010 - 550 - 10V 10%
OsramOTi 85/347-480/2A3 DIM-1LHB AUXUL85347 - 480700 -230010 - 550 - 10V 10%
OsramOTi 85/347-480/2A3 DIM-1 L AUXUL85347-480700 - 230010 - 550 - 10V 10%
OsramOTi 95W/UNV/2750C/2DIM+/P6/AUXUL95347-480700 - 275015 - 540 - 10V 1%
        

This solution with the XSR bridge is only for 2-wire sensors; the 2-wire sensor connects to the XSR bridge. See the line diagram SU-5 (2-wire) with XSR Bridge and (347v) 0-10v Driver (03066-02), which is the most preferred solution.  

An alternative method, when energy metering is not required, uses a 347 VAC Profile 0 driver with an 8-pin sensor and adapter cable. In this case, the sensor is powered from the Auxiliary DC supply of the driver. Refer to the following line diagrams:

Recommended article: