Install Guide
View the files at the bottom of the page to download the Micro Sensor with 2-wire Adaptor (KIT-SU-5E-D) - Install Guide.
Overview
The Enlighted Micro Sensor with 2-wire Adaptor delivers all the functionality of our other sensors in a minimally-sized package. It is designed to be easily mounted into lighting fixtures or ceiling tiles such that only the discreet white faceplate is visible. The sensor slides into a carrier sleeve, fitting a standard 1/2 inch trade size knockout or 7/8 inch (22 mm) hole. Carrier sleeves compatible with either lighting fixtures or ceiling tiles are available. Sensor replacement requires no tools—slide the sensor out of the carrier, unplug the connector, and install the new sensor.
Micro Sensor with 2-wire Adaptor Cable
The following sections describe installing the Micro sensor 2-Wire adaptor in a fixture or tile.
If you have purchased the Hard Ceiling Mount Carrier (HCMC-SU-5E) as an optional component for installing the sensor, refer to the following articles:
Installation
Shipped Components
Supplemental Components
Tools you may Need
- 7/8” Drill bit (1/2” knock out trade size)
- Hand drill
- Wire stripper
* Indicated products are sold separately. Contact Enlighted Customer Support.
Caution
A qualified electrician must perform the installation and maintenance under the local, state, and national electrical codes (NEC) and requirements.
Warning

- FELV circuits are not safe to touch.

- Isolate the circuits connected to any FELV source from the AC mains supply of the control gear.
- Ensure to protect the FELV circuit from any accidental contact.

- When installing the sensors, de-energize the FELV source and any AC main sources near the FELV.
- Place the sensors in a secure location, such as in the ceiling near a luminaire, with the cabling above the ceiling or within the luminaire.
- The NEC considers electrical equipment installed a minimum of 8 ft (2.5 m) off the floor to be suitably guarded against accidental contact.
- Circuits connected to any FELV control terminal must be insulated for the LV supply voltage of the control gear, and all terminals connected to the FELV circuit must be protected from accidental contact.
Fixture Mount Sensor Installation (Approved for Class 2, SELV and FELV Installations)
Note: For fixture mounting, use the fixture carrier and nut that is shipped with the sensor. The fixture mount can accommodate up to 0.25” (6.35 mm) thickness materials.

Fixture Carrier and Nut
Step 1: De-energize the luminaire.![]()
Step 2: Determine the sensor's location in the fixture and cut a ½ inch (7/8” or 23 mm diameter) knockout in the fixture.

![]()
Step 3: Insert the fixture carrier through the hole in the fixture.![]()
Step 4: From behind the fixture, align the tabs of the nut with the keys on the fixture carrier.

Step 5: Slide the tabs of the nut along with the keys of the carrier to fasten the carrier.


Step 6: Connect the adaptor cable to the sensor.

Step 7: Cut two lengths of 18 AWG (0.75 mm2) solid wire of the required length. Strip each end of the two wires leaving 5/16" (8 mm) of exposed wire.
Step 8: Insert one end of the pair of wires through the hole in the fixture and connect the wires to the sensor.

Step 9: Guiding the wire from above, push the sensor into the carrier until it securely clicks into the carrier.

Step 10: Leave four inches of slack cable in the sequence loop to avoid pinching the cable and bring the sensor down if it needs to be replaced.
Note: Do not pull the cable forcefully, as this might damage the cable or connector.
Step 11: See section Connecting the Cable to the LED Driver.
Tile Mount Sensor Installation (Approved for Class 2, SELV and NOT approved for FELV Installations)
Note: For tile mounting, the tile carrier and nut must be ordered separately. The tile mount can accommodate up to 1.5” (38 mm) thick tiles.

Tile Carrier and Nut
Step 1: De-energize the luminaire.
Step 2: Make a 7/8" or 23 mm diameter hole in the ceiling tile.
Step 3: Insert the tile carrier through the hole into the tile.

![]()
Step 4: Thread the plain end of the nut from behind the tile to secure the carrier.

![]()
If the tile is thicker than normal, flip the nut and thread the nut's ribbed end to secure the carrier.
Step 5: Insert the adaptor cable into the sensor.

Step 6: Cut two lengths of 18 AWG (0.75 mm2) solid wire of the required length. Strip each end of the two wires leaving 5/16" (8 mm) of exposed wire.
Step 7: Insert one end of the wires through the hole in the tile and connect the wires to the sensor.

Step 8: Guiding the wire from above, push the sensor into the carrier until it securely clicks into the carrier.

Step 9: Leave four inches of slack cable in the sequence loop to avoid pinching the cable and bring the sensor down if it needs to be replaced.
Note: Do not pull the cable forcefully, as this might damage the cable or connector.
Step 10: See section Connecting the Cable to the LED Driver.
Connecting the Cable to the LED Driver
Step 1: Connect the other end of the pair of wires to the LED Driver.

Step 2: Turn the power on by switching on the circuit breaker and wait for the green LED to appear.
LED Description
LED Status | Description/Solution |
LED not on | The sensor is not powered on.Check power and wiring. |
Blinking Green | The commissioned sensor has powered up and has detected motion. If there is no motion in the sensor’s field of view, the blinking will stop. Wave your hands below the sensor to restart LED blinking. |
Solid Green | The uncommissioned sensor has powered up successfully and completed the wiring test with no unexpected conditions – waiting for discovery. |
Blinking Red | The uncommissioned sensor has powered up and completed the wiring test with one or more conditions unexpected of a typical LED fixture – waiting for discovery. |
Solid Red | Faulty sensor – replace the sensor. |
Solid Blue | The sensor received a request to identify itself. |
Blinking Blue | The uncommissioned sensor powered up successfully, but the sensor is unable to detect an energy measurement device (CU or Driver), waiting for discovery. |
Blinking Magenta | When the sensor is connected to a DALI emergency driver that is currently in the process of an emergency test or an emergency test pending. |
Interrupted Green | Un-commissioned fixtureless sensors. |
Product Compliance



Model No: SU-5E-01
Product Code: KIT-SU-5E-D-xxx
xxx: IoT Note (IoT), Connected Lighting (CL)
FCC ID: AQQ-SU5E
IC: 10138A-SU5E
Rev.07
DoCs