Install Guide
View the file at the bottom of the page to download the Micro Sensor, 2-wire (SU-6E-2W) - Install Guide.
Overview
The Enlighted Gen 6 Micro Sensor (product code SU-6E-2W) is designed to be easily mounted into lighting fixtures or ceiling tiles, such that only the discreet white faceplate is visible. The sensor slides into a carrier sleeve, fitting a standard 1/2 inch trade size knockout or 7/8 inch (22 mm) hole. Carrier sleeves compatible with either lighting fixtures or ceiling tiles are available. Sensor replacement requires no tools—simply slide the sensor out of the carrier, unplug the connector, and install the new sensor.
Micro Sensor and Carrier
The following sections describe installing the 2-wire Micro Sensor in a fixture or tile.
If you have purchased the Hard Ceiling Mount Carrier (product code HCMC-SU-5E) as an optional component for installing the SU-6E sensor, refer to the following articles:
- Hard Ceiling Mount Carrier (HCMC-SU-5E) - Spec Sheet
- Hard Ceiling Mount Carrier (HCMC-SU-5E) - Install Guide
Installation
Shipped Components: Micro Sensor, 2-wire (SU-6E-2W) - Spec Sheet
Supplemental Components:
- Micro Sensor Tile Mount Carrier (TMC-SU-5E) - Spec Sheet
- Hard Ceiling Mount Carrier (HCMC-SU-5E) - Spec Sheet
Tools you may need
- 7/8” drill bit (1/2” knock out trade size)
- Hand drill
Caution
A qualified electrician must perform installation and maintenance per local, state, and national electrical codes (NEC) and requirements.
Installation Procedure
Before proceeding with the sensor installation, make sure to de-energize the luminaire.
Note: When replacing the white bezel with the black bezel, make sure the bezel is securely fastened in place so that the key is properly seated in the slot.
Fixture Mount Installation
Note: For fixture mounting, use the fixture carrier and nut that is shipped with the sensor. The fixture mount can accommodate up to 0.25” thickness materials.
Fixture Carrier and Nut
Step 1: De-energize the luminaire.
Step 2: Determine the sensor's location in the fixture and cut a ½ inch (7/8” diameter) knockout in the fixture.
Step 3: Insert the fixture carrier through the hole in the fixture.
Step 4: From behind the fixture, align the tabs of the nut with the keys on the fixture carrier.
Step 5: Slide the tabs of the nut along with the keys of the carrier to fasten the carrier.
Step 6: Insert the 2 wire end of the sensor cable through the carrier.
Step 7: Connect the 2 wire end to the sensor.
Step 8: Guiding the wire from above, push the sensor into the carrier until it securely clicks into the carrier.
Step 9: Leave four inches of slack cable in the sequence loop to avoid pinching the cable and to bring the sensor down if it needs to be replaced.
Note: Do not pull the cable forcefully, as this might damage the cable or connector.
Tile Mount Installation
Note: For tile mounting, the tile carrier and nut must be ordered separately. The tile mount can accommodate up to 1.5” thick tiles.
Tile Carrier and Nut
Step 1: De-energize the luminaire.
Step 2: Make a 7/8th diameter hole in the ceiling tile.
Step 3: Insert the tile carrier through the hole into the tile.
Step 4: Thread the plain end of the nut from behind the tile to secure the carrier.
If the tile is thicker than normal, flip the nut and thread the nut's ribbed end to secure the carrier.
Step 5: Insert the 2 wire end of the sensor cable through the carrier.
Step 6: Connect the 2 wire end to the sensor.
Step 7: Guiding the wire from above, push the sensor into the carrier until it securely clicks into the carrier.
Step 8: Leave four inches of slack cable in the sequence loop to avoid pinching the cable and to bring the sensor down if it needs to be replaced.
Note: Do not pull the cable forcefully, as this might damage the cable or connector.
LED Description
LED Status | Description/Solution |
LED not on | The sensor is not powered on. Check power and wiring. |
Blinking Green | The commissioned sensor has powered up and has detected motion. If there is no motion in the sensor’s field of view, the blinking will stop. Wave your hands below the sensor to restart LED blinking. |
Solid Green | The uncommissioned sensor has powered up successfully and completed the wiring test with no unexpected conditions – waiting for discovery. |
Blinking Red | The uncommissioned sensor has powered up and completed the wiring test with one or more conditions unexpected of a typical LED fixture – waiting for discovery. |
Solid Red | Faulty sensor – replace the sensor. |
Solid Blue | The Sensor received a request to identify itself. |
Blinking Blue | The uncommissioned sensor powered up successfully, but the sensor is unable to detect an energy measurement device (CU or Driver), waiting for discovery. |
Interrupted Green | Un-commissioned fixtureless sensors. |
Product Compliance
Model No: SU-6E-2W
Product Code: SU-6e-xxx
xxx: IoT Note (IoT), Connected Lighting (CL), Independent Lighting/Enlighted One (IL)
FCC ID: AQQ-SU6E
IC: 10138A-SU6E
Rev.01