Download the PICS PDF from the Attachments section.
Overview
The Enlighted Lighting BACnet/IP interface enables BACnet/IP-based integration between the Enlighted lighting control network and any BACnet® compatible Building Management System (BMS). The Lighting BACnet/IP software installed in Enlighted Manage provides seamless integration between the Enlighted network and the BMS system via BACnet.
BACnet/IP Protocol Implementation Conformance Statement (Annex A)
Date | 42917 |
Vendor Name | Enlighted Inc. |
Product Name | BACnet Interface for Enlighted Systems |
Model Name | BIES-01 |
BACnet Device Profile | B-ASC, B-RTR |
Product Codes | NB-BS-01 (Base License: BACnet SW and EM points) NB-GP-01 (Group Points License: Area Group points) NG-SP-01 (Individual Points License: Fixture & Plugload points) |
Firmware Revision: | 1.1 |
BACnet Protocol Version | 1 |
BACnet Protocol Revision: | 14 |
Product Description | Lighting and HVAC Monitoring and Management Systems. |
BACnet Standardized Device Profile (Annex L)
| BACnet Operator Workstation (B-OWS) | | BACnet Advanced Application Controller (B-AAC) |
| BACnet Advanced Operator Workstation (B-AWS) | X | BACnet Application Specific Controller (B-ASC) |
| BACnet Operator Display (B-OD) | | BACnet Smart Sensor (B-SS) |
| BACnet Building Controller (B-BC) | | BACnet Smart Actuator (B-SA) |
BACnet/IP Interoperability Building Blocks Supported (Annex K)
DS-RP-B Data Sharing – Read Property B | DM-DDB-B Device Management – Dynamic Device Binding B |
DS-WS-B Data Sharing – Write Property B | DM-DOB-B Device Management – Dynamic Object Binding B |
DS-RPM-B Data Sharing – Read Property Multiple-B | DM-DCC-B Device Management – Device Communication Control B |
Segmentation Capability
Able to transmit segmented messages | Window Size |
Able to receive the segmented message | Window Size |
Standard Object Types Supported
Object Type Supported | Can be Created Dynamically | Can be Deleted Dynamically |
Analog Input | No | No |
Analog Value | No | No |
Analog Output | No | No |
Device | No | No |
Binary Input | No | No |
Binary Value | No | No |
Optional Properties Supported
Device Object: Description
All Other Objects: Description
Data Link Layer Options
X | BACnet IP, (Annex J) | | MS/TP slave (Clause 9), baud rate(s): |
| BACnet IP, (Annex J), Foreign Device | | Point-To-Point, EIA 232 (Clause 10), baud rate(s): |
| ISO 8802-3, Ethernet (Clause 7) | | Point-To-Point, modem, (Clause 10), baud rate(s): |
| ATA 878.1, 2.5 Mb. ARCNET (Clause 8) | | LonTalk, (Clause 11), medium: |
| ATA 878.1, EIA-485 ARCNET (Clause 8), baud rate(s): | | BACnet/ZigBee (ANNEX O) |
| MS/TP master (Clause 9), baud rate(s): | | Other: |
Device Address Binding
Is static device binding supported? (This is necessary for two-way communication with MS/TP slaves and certain other devices.): NO
Networking Options
Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc.
Annex H, BACnet Tunneling Router over IP
BACnet/IP Broadcast Management Device (BBMD)
Does the BBMD support registrations by Foreign Devices?
Yes
No
Does the BBMD support network address translation?
Yes
No
Network Security Options:
Non-secure Device - is capable of operating without BACnet Network Security.
Secure Device - is capable of using BACnet Network Security (NS-SD BIBB)
Multiple Application-Specific Keys:
Supports encryption (NS-ED BIBB)
Key Server (NS-KS BIBB)
Character Sets Supported
Indicating support for multiple character sets does not imply that they can all be supported simultaneously.
X | ISO 10646 (UTF-8) | | IBMTM/MicrosoftTM DBCS | | ISO 8859-1 |
| ISO 10646 (UCS-2) | | ISO 10646 (UCS-4) | | JIS X 0208 |
If this product is a communication gateway, describe the types of non-BACnet equipment/networks(s) that the gateway supports: NA.
Enlighted Lighting – BACnet/IP Object Mapping
Enlighted BACnet Lighting exposes the following Enlighted Lighting objects over BACnet/IP. After the module is installed in Manage, the lighting objects can be monitored and controlled via BACnet/IP interface.
Lighting BACnet/IPObject | Object Description | Unit | Access | BACnet/IP Object Type | Device ID |
Base Points (Manage) - The physical/virtual Manage system includes all sensors, areas, and groups |
Manage Energy Consumption – Lighting | Total energy consumption of all lights | Watt-Hour (15 minutes) | Read/CoV | Analog Input | Derived from EM Base ID* |
Manage Energy Consumption – Plugload | Total energy consumption of all plugloads | Watt-Hour (15 minutes) | Read/CoV | Analog Input |
Manage DR Level | Sensitivity to respond to a DR event. 1: High 2: Medium 3: Low 4: Special | N/A | Write | Analog Value |
Manage DR Duration | Duration of schedule DR event | Minutes (must be a whole number) | Write | Analog Value |
Manage Emergency Status | In an Emergency, lights are turned on or off in the building 0: Off – Lights switch to Auto mode light levels based on their fixture profile 1: On – Lights set to a maximum level of 100% | Binary | Write | Boolean Value |
Gateway Outage Count | Count of gateways not currently communicating on the system | Count | Read/CoV | Analog Input | |
Group Points (Area) - Area is a group of devices on a floor |
Area Energy Consumption – Lighting | Total energy consumption in the area | Watt-Hour (15 minutes) | Read/CoV | Analog Input | Derived from Area Base ID* |
Area Energy Consumption – Plugload | Total energy consumption of the plugload | Watt-Hour (15 minutes) | Read/CoV | Analog Input |
Area Occupancy Status | State of occupancy 0: Unoccupied in an area 1: Occupied | Binary | Read/CoV | Binary Input |
Area Emergency Status – On/off | In an Emergency, lights are turned on or off in the area 0: Off – Lights in the area switch to Auto light levels based on their fixture light profile 1: On – Lights in the area are set to a maximum level of 100% | N/A | Write | Boolean Value |
Area Lighting Control |
Controls light levels for ‘AreaManualOverrideDuration’ minutes 0: Lights off 1-99: Dim Level 100: Lights full-on, set to 100% 101: Auto – Normal light levels for a commissioned fixture based on its profile.
Note: The Profile Ramp-up time affects override commands issued via API/BACnet. The override command will take effect after the ramp-up time set in the profile ends.
| Percent (must be a whole number) | Write | Analog Value |
Area Override | Activates Holiday Override Profile as configured in Manage, for 'AreaManualOverrideDuration' minutes. | N/A | Write | Analog Value |
Group Points (Switch) - Switch Group is a group of devices on a floor that are controlled together by one or more switches/ERCs |
Switch Group Scene |
Triggers a given scene override for 1 hour
| N/A | Write | Analog Value | Derived from Switch Base ID* |
*EM Base ID is the BACnet base address used by the devices on the floor. Area Base ID is the BACnet base address used by the devices in the area.
Lighting BACnet/IPObject | Object Description | Unit | Access | BACnet/IP Object Type | Instance ID |
Individual Points (Fixtures) |
Fixture Energy Consumed | Energy consumed by the fixture | Watt-Hour (15 minutes) | Read/CoV | Analog Input | Derived from Sensor ID |
Fixture Dim Level | Light output level 0: Lights Off 100%: Lights Full-on | Percent (must be a whole number) | Read/Write/CoV | Analog Value |
Fixture Temperature | Air temperature value at the sensor | Fahrenheit | Read/CoV | Analog Input |
Individual Points (Plugloads) |
Plugload Energy Consumed | Energy consumed by the managed and unmanaged plugload | Watt-Hour (15 minutes) | Read/CoV | Analog Input | Derived from Sensor ID |
Plugload On/Off | State of the plugload 0: Plugload Off 1: Plugload On | Binary | Read/Write/CoV | Binary Value | Derived from Sensor ID |
Note: The BACnet IP polls every five minutes to obtain data for all inputs.
Using Switch Group Scene Point:
In the example below, if the user wants to control the switch group, TM_ALL_20 scene, (all lights are at 20 percent dim), the BACnet client should send the value ‘4’ to the (Siemens/Campus 1/Building 11/Floor 111/SWITCH-SW-TEST (Device: 2200004).

Downloads: