Download the PICS PDF from the Attachments section.
Overview
The Enlighted Lighting BACnet/IP interface enables BACnet/IP-based integration between the Enlighted lighting control network and any BACnet® compatible Building Management System (BMS). The Lighting BACnet/IP software installed in Enlighted Manage provides seamless integration between the Enlighted network and the BMS system via BACnet.
BACnet/IP Protocol Implementation Conformance Statement (Annex A)
| Date | 42917 |
| Vendor Name | Enlighted Inc. |
| Product Name | BACnet Interface for Enlighted Systems |
| Model Name | BIES-01 |
| BACnet Device Profile | B-ASC, B-RTR |
| Product Codes | NB-BS-01 (Base License: BACnet SW and EM points) NB-GP-01 (Group Points License: Area Group points) NG-SP-01 (Individual Points License: Fixture & Plugload points) |
| Firmware Revision: | 1.1 |
| BACnet Protocol Version | 1 |
| BACnet Protocol Revision: | 14 |
| Product Description | Lighting and HVAC Monitoring and Management Systems. |
BACnet Standardized Device Profile (Annex L)
| | BACnet Operator Workstation (B-OWS) | | BACnet Advanced Application Controller (B-AAC) |
| | BACnet Advanced Operator Workstation (B-AWS) | X | BACnet Application Specific Controller (B-ASC) |
| | BACnet Operator Display (B-OD) | | BACnet Smart Sensor (B-SS) |
| | BACnet Building Controller (B-BC) | | BACnet Smart Actuator (B-SA) |
BACnet/IP Interoperability Building Blocks Supported (Annex K)
| DS-RP-B Data Sharing – Read Property B | DM-DDB-B Device Management – Dynamic Device Binding B |
| DS-WS-B Data Sharing – Write Property B | DM-DOB-B Device Management – Dynamic Object Binding B |
| DS-RPM-B Data Sharing – Read Property Multiple-B | DM-DCC-B Device Management – Device Communication Control B |
Segmentation Capability
| Able to transmit segmented messages | Window Size |
| Able to receive the segmented message | Window Size |
Standard Object Types Supported
| Object Type Supported | Can be Created Dynamically | Can be Deleted Dynamically |
| Analog Input | No | No |
| Analog Value | No | No |
| Analog Output | No | No |
| Device | No | No |
| Binary Input | No | No |
| Binary Value | No | No |
Optional Properties Supported
Device Object: Description
All Other Objects: Description
Data Link Layer Options
| X | BACnet IP, (Annex J) | | MS/TP slave (Clause 9), baud rate(s): |
| | BACnet IP, (Annex J), Foreign Device | | Point-To-Point, EIA 232 (Clause 10), baud rate(s): |
| | ISO 8802-3, Ethernet (Clause 7) | | Point-To-Point, modem, (Clause 10), baud rate(s): |
| | ATA 878.1, 2.5 Mb. ARCNET (Clause 8) | | LonTalk, (Clause 11), medium: |
| | ATA 878.1, EIA-485 ARCNET (Clause 8), baud rate(s): | | BACnet/ZigBee (ANNEX O) |
| | MS/TP master (Clause 9), baud rate(s): | | Other: |
Device Address Binding
Is static device binding supported? (This is necessary for two-way communication with MS/TP slaves and certain other devices.): NO
Networking Options
Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc.
Annex H, BACnet Tunneling Router over IP
BACnet/IP Broadcast Management Device (BBMD)
Does the BBMD support registrations by Foreign Devices?
Yes
No
Does the BBMD support network address translation?
Yes
No
Network Security Options:
Non-secure Device - is capable of operating without BACnet Network Security.
Secure Device - is capable of using BACnet Network Security (NS-SD BIBB)
Multiple Application-Specific Keys:
Supports encryption (NS-ED BIBB)
Key Server (NS-KS BIBB)
Character Sets Supported
Indicating support for multiple character sets does not imply that they can all be supported simultaneously.
| X | ISO 10646 (UTF-8) | | IBMTM/MicrosoftTM DBCS | | ISO 8859-1 |
| | ISO 10646 (UCS-2) | | ISO 10646 (UCS-4) | | JIS X 0208 |
If this product is a communication gateway, describe the types of non-BACnet equipment/networks(s) that the gateway supports: NA.
Enlighted Lighting – BACnet/IP Object Mapping
Enlighted BACnet Lighting exposes the following Enlighted Lighting objects over BACnet/IP. After the module is installed in Manage, the lighting objects can be monitored and controlled via BACnet/IP interface.
| Lighting BACnet/IPObject | Object Description | Unit | Access | BACnet/IP Object Type | Device ID |
| Base Points (Manage) - The physical/virtual Manage system includes all sensors, areas, and groups |
| Manage Energy Consumption – Lighting | Total energy consumption of all lights | Watt-Hour (15 minutes) | Read/CoV | Analog Input | Derived from EM Base ID* |
| Manage Energy Consumption – Plugload | Total energy consumption of all plugloads | Watt-Hour (15 minutes) | Read/CoV | Analog Input |
| Manage DR Level | Sensitivity to respond to a DR event. 1: High 2: Medium 3: Low 4: Special | N/A | Write | Analog Value |
| Manage DR Duration | Duration of schedule DR event | Minutes (must be a whole number) | Write | Analog Value |
| Manage Emergency Status | In an Emergency, lights are turned on or off in the building 0: Off – Lights switch to Auto mode light levels based on their fixture profile 1: On – Lights set to a maximum level of 100% | Binary | Write | Boolean Value |
| Gateway Outage Count | Count of gateways not currently communicating on the system | Count | Read/CoV | Analog Input | |
| Group Points (Area) - Area is a group of devices on a floor |
| Area Energy Consumption – Lighting | Total energy consumption in the area | Watt-Hour (15 minutes) | Read/CoV | Analog Input | Derived from Area Base ID* |
| Area Energy Consumption – Plugload | Total energy consumption of the plugload | Watt-Hour (15 minutes) | Read/CoV | Analog Input |
| Area Occupancy Status | State of occupancy 0: Unoccupied in an area 1: Occupied | Binary | Read/CoV | Binary Input |
| Area Emergency Status – On/off | In an Emergency, lights are turned on or off in the area 0: Off – Lights in the area switch to Auto light levels based on their fixture light profile 1: On – Lights in the area are set to a maximum level of 100% | N/A | Write | Boolean Value |
| Area Lighting Control |
Controls light levels for ‘AreaManualOverrideDuration’ minutes 0: Lights off 1-99: Dim Level 100: Lights full-on, set to 100% 101: Auto – Normal light levels for a commissioned fixture based on its profile.
Note: The Profile Ramp-up time affects override commands issued via API/BACnet. The override command will take effect after the ramp-up time set in the profile ends.
| Percent (must be a whole number) | Write | Analog Value |
| Area Override | Activates Holiday Override Profile as configured in Manage, for 'AreaManualOverrideDuration' minutes. | N/A | Write | Analog Value |
| Group Points (Switch) - Switch Group is a group of devices on a floor that are controlled together by one or more switches/ERCs |
| Switch Group Scene |
Triggers a given scene override for 1 hour
| N/A | Write | Analog Value | Derived from Switch Base ID* |
*EM Base ID is the BACnet base address used by the devices on the floor. Area Base ID is the BACnet base address used by the devices in the area.
| Lighting BACnet/IPObject | Object Description | Unit | Access | BACnet/IP Object Type | Instance ID |
| Individual Points (Fixtures) |
| Fixture Energy Consumed | Energy consumed by the fixture | Watt-Hour (15 minutes) | Read/CoV | Analog Input | Derived from Sensor ID |
| Fixture Dim Level | Light output level 0: Lights Off 100%: Lights Full-on | Percent (must be a whole number) | Read/Write/CoV | Analog Value |
| Fixture Temperature | Air temperature value at the sensor | Fahrenheit | Read/CoV | Analog Input |
| Individual Points (Plugloads) |
| Plugload Energy Consumed | Energy consumed by the managed and unmanaged plugload | Watt-Hour (15 minutes) | Read/CoV | Analog Input | Derived from Sensor ID |
| Plugload On/Off | State of the plugload 0: Plugload Off 1: Plugload On | Binary | Read/Write/CoV | Binary Value | Derived from Sensor ID |
Note: The BACnet IP polls every five minutes to obtain data for all inputs.
Using Switch Group Scene Point:
In the example below, if the user wants to control the switch group, TM_ALL_20 scene, (all lights are at 20 percent dim), the BACnet client should send the value ‘4’ to the (Siemens/Campus 1/Building 11/Floor 111/SWITCH-SW-TEST (Device: 2200004).

Downloads: