Salesforce

BACnet Interface for Enlighted Systems-PICS

« Go Back
Information
BACnet Interface for Enlighted Systems-PICS
ka03o000001Du5jAAC
Article Details

Download the PICS PDF from the Attachments section.

Overview

The Enlighted Lighting BACnet/IP interface enables BACnet/IP-based integration between the Enlighted lighting control network and any BACnet® compatible Building Management System (BMS). The Lighting BACnet/IP software installed in Enlighted Manage provides seamless integration between the Enlighted network and the BMS system via BACnet.

BACnet/IP Protocol Implementation Conformance Statement (Annex A)

Date       42917
Vendor Name      Enlighted Inc.
Product NameBACnet Interface for Enlighted Systems
Model NameBIES-01
BACnet Device ProfileB-ASC, B-RTR
Product CodesNB-BS-01 (Base License: BACnet SW and EM points)
NB-GP-01 (Group Points License: Area Group points)
NG-SP-01 (Individual Points License: Fixture & Plugload points)
Firmware Revision:1.1
BACnet Protocol Version1
BACnet Protocol Revision:14
Product DescriptionLighting and HVAC Monitoring and Management Systems.

BACnet Standardized Device Profile (Annex L)

 BACnet Operator Workstation (B-OWS) BACnet Advanced Application Controller (B-AAC)
 BACnet Advanced Operator Workstation (B-AWS)XBACnet Application Specific Controller (B-ASC)
 BACnet Operator Display (B-OD) BACnet Smart Sensor (B-SS)
 BACnet Building Controller (B-BC) BACnet Smart Actuator (B-SA)

BACnet/IP Interoperability Building Blocks Supported (Annex K)

DS-RP-B Data Sharing – Read Property BDM-DDB-B Device Management – Dynamic Device Binding B
DS-WS-B Data Sharing – Write Property BDM-DOB-B Device Management – Dynamic Object Binding B
DS-RPM-B Data Sharing – Read Property Multiple-BDM-DCC-B Device Management – Device Communication Control B

Segmentation Capability

Able to transmit segmented messagesWindow Size
Able to receive the segmented messageWindow Size

Standard Object Types Supported

Object Type SupportedCan be Created DynamicallyCan be Deleted Dynamically
Analog InputNoNo
Analog ValueNoNo
Analog OutputNoNo
DeviceNoNo
Binary InputNoNo
Binary ValueNoNo

Optional Properties Supported

Device Object: Description

All Other Objects: Description

Data Link Layer Options

XBACnet IP, (Annex J) MS/TP slave (Clause 9), baud rate(s):  
 BACnet IP, (Annex J), Foreign Device Point-To-Point, EIA 232 (Clause 10), baud rate(s):
 ISO 8802-3, Ethernet (Clause 7) Point-To-Point, modem, (Clause 10), baud rate(s):
 ATA 878.1, 2.5 Mb. ARCNET (Clause 8) LonTalk, (Clause 11), medium:
 ATA 878.1, EIA-485 ARCNET (Clause 8), baud rate(s): BACnet/ZigBee (ANNEX O)
 MS/TP master (Clause 9), baud rate(s): Other:

Device Address Binding

Is static device binding supported? (This is necessary for two-way communication with MS/TP slaves and certain other devices.): NO

Networking Options

Chekd_Chkbox.png Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc.

Empty_Chkbox.png Annex H, BACnet Tunneling Router over IP

Empty_Chkbox.png BACnet/IP Broadcast Management Device (BBMD)

                Does the BBMD support registrations by Foreign Devices?            Empty_Chkbox.png Yes  Empty_Chkbox.png No

                Does the BBMD support network address translation?                  Empty_Chkbox.png Yes  Empty_Chkbox.png No

Network Security Options:

Chekd_Chkbox.png Non-secure Device - is capable of operating without BACnet Network Security.

Empty_Chkbox.png Secure Device - is capable of using BACnet Network Security (NS-SD BIBB)

    Empty_Chkbox.png Multiple Application-Specific Keys:

    Empty_Chkbox.png Supports encryption (NS-ED BIBB)

    Empty_Chkbox.png Key Server (NS-KS BIBB)

Character Sets Supported

Indicating support for multiple character sets does not imply that they can all be supported simultaneously.

XISO 10646 (UTF-8) IBMTM/MicrosoftTM DBCS ISO 8859-1
 ISO 10646 (UCS-2) ISO 10646 (UCS-4) JIS X 0208

If this product is a communication gateway, describe the types of non-BACnet equipment/networks(s) that the gateway supports: NA.

Enlighted Lighting – BACnet/IP Object Mapping

Enlighted BACnet Lighting exposes the following Enlighted Lighting objects over BACnet/IP. After the module is installed in Manage, the lighting objects can be monitored and controlled via BACnet/IP interface.

Lighting BACnet/IPObjectObject Description UnitAccessBACnet/IP Object TypeDevice ID
Base Points (Manage) - The physical/virtual Manage system includes all sensors, areas, and groups
Manage Energy Consumption – LightingTotal energy consumption of all lights Watt-Hour
(15 minutes)
Read/CoVAnalog InputDerived from EM Base ID*
Manage Energy Consumption – PlugloadTotal energy consumption of all plugloadsWatt-Hour
(15 minutes)
Read/CoVAnalog Input
Manage DR LevelSensitivity to respond to a DR event. 
1: High
2: Medium
3: Low
4: Special
N/AWriteAnalog Value
Manage DR DurationDuration of schedule DR eventMinutes (must be a whole number)WriteAnalog Value
Manage Emergency StatusIn an Emergency, lights are turned on or off in the building
0: Off – Lights switch to Auto mode light levels based on their fixture profile
1: On – Lights set to a maximum level of 100%
BinaryWriteBoolean Value
Gateway Outage CountCount of gateways not currently communicating on the systemCountRead/CoVAnalog Input 
Group Points (Area) - Area is a group of devices on a floor
Area Energy Consumption – LightingTotal energy consumption in the areaWatt-Hour
(15 minutes)
Read/CoVAnalog InputDerived from Area Base ID*
Area Energy Consumption – PlugloadTotal energy consumption of the plugloadWatt-Hour
(15 minutes)
Read/CoVAnalog Input
Area Occupancy Status State of occupancy
0: Unoccupied in an area
1: Occupied
BinaryRead/CoVBinary Input
Area Emergency Status – On/offIn an Emergency, lights are turned on or off in the area
0: Off – Lights in the area switch to Auto light levels based on their fixture light profile
1: On – Lights in the area are set to a maximum level of 100%
N/AWriteBoolean Value
Area Lighting Control

Controls light levels for ‘AreaManualOverrideDuration’ minutes

0: Lights off
1-99: Dim Level
100: Lights full-on, set to 100%
101: Auto – Normal light levels for a commissioned fixture based on its profile.

Note: The Profile Ramp-up time affects override commands issued via API/BACnet. The override command will take effect after the ramp-up time set in the profile ends.  

Percent (must be a whole number)WriteAnalog Value
Area OverrideActivates Holiday Override Profile as configured in Manage, for 'AreaManualOverrideDuration' minutes.N/AWriteAnalog Value
Group Points (Switch) - Switch Group is a group of devices on a floor that are controlled together by one or more switches/ERCs
Switch Group Scene

Triggers a given scene override for 1 hour

N/AWriteAnalog ValueDerived from Switch Base ID*

*EM Base ID is the BACnet base address used by the devices on the floor. Area Base ID is the BACnet base address used by the devices in the area.

Lighting BACnet/IPObjectObject Description UnitAccessBACnet/IP Object TypeInstance ID
Individual Points (Fixtures)
Fixture Energy ConsumedEnergy consumed by the fixtureWatt-Hour
(15 minutes)
Read/CoVAnalog InputDerived from Sensor ID
Fixture Dim LevelLight output level
0: Lights Off
100%: Lights Full-on
Percent (must be a whole number)Read/Write/CoVAnalog Value
Fixture TemperatureAir temperature value at the sensorFahrenheitRead/CoVAnalog Input
Individual Points (Plugloads)
Plugload Energy ConsumedEnergy consumed by the managed and unmanaged plugloadWatt-Hour
(15 minutes)
Read/CoVAnalog InputDerived from Sensor ID
Plugload On/OffState of the plugload
0: Plugload Off
1: Plugload On
 BinaryRead/Write/CoVBinary ValueDerived from Sensor ID

Note: The BACnet IP polls every five minutes to obtain data for all inputs. 

Using Switch Group Scene Point: 

In the example below, if the user wants to control the switch group, TM_ALL_20 scene, (all lights are at 20 percent dim), the BACnet client should send the value  ‘4’ to the (Siemens/Campus 1/Building 11/Floor 111/SWITCH-SW-TEST (Device: 2200004).

Switch_Grp_SceneID.png

Downloads:


Powered by