Contact Closure FAQ

« Go Back
Information
Contact Closure FAQ
Contact-Closure-FAQ
Article Details

 

DCC Inputs with On-prem Manage

Is it possible to install Contact Closure on an EMC?

No. The Contact Closure cannot be installed on an EMC. It can only be installed on an on-prem Manage  as the Contact Closure needs to obtain the IP address from an on-prem Manage. The EMC gets its IP address from the customer network.

Can you program a Contact Closure to Manage if the Contact Closure is getting DHCP from a customer network? 

No. The Contact Closure must get the IP address from an on-prem Manage DHCP. This applies to all models: Manage, Midrange Manage, Enterprise Manage. 

How many of the Contact Closure devices can be configured to Manage?

Up to a maximum of ten Contact Closures can be connected to a Manage via the Gateway network to one of the Ethernet ports on the PoE Switch. Refer to Contact Closure (ENL-DCC-01) - Spec Sheet.

Is the Contact Closure shipped with a power adapter?

Yes. The Barionet 50 contact closure is shipped with a 24V power supply. Refer to www.barix.com.

DCC Inputs with Enlighted Edge and On-prem Manage/EMC

NOTE: The Enlighted lighting network must include the Enlighted Edge installed so on-Prem Manage/EMC can detect the Barix devices discovered by Edge.

Is it possible to provide Dry Contact Closure inputs to an EMC Instance?

Yes. DCC inputs to an on-prem Manage/EMC instance are possible through the Enlighted Edge.

Can you program a Dry Contact Closure through the Enlighted Edge to Manage if the Contact Closure is getting DHCP from a customer network? 

Yes. Contact Closure gets the IP address from the customer’s network, and the Barix Dry CC is discovered by Enlighted Edge. 

How many of the Contact Closure devices can be configured by Manage?

Up to a maximum of ten Contact Closures can be connected to a Manage via the Gateway network to one of the Ethernet ports on the PoE Switch. Refer to Contact Closure (ENL-DCC-01) - Spec Sheet.

Is the Contact Closure shipped with a power adapter?

Yes. The Barionet 50 contact closure is shipped with a 24V power supply. Refer to www.barix.com.