UL924 ESRLBCND Device with Control Unit - No Emergency Energy Metering (03166-04)
This diagram shows a fixture with both emergency and normal segments being controlled via a single sensor, a single Control Unit, and a single UL924 device. Note that energy metering of the emergency segment at any time (normal or emergency operation) will not be available. The advantage is that there is only a single Sensor and CU required for all segments, and all segments are fully dimmable and can be turned ON/OFF during normal operation.
NOTE: The ESRLBCND is preferred over the ESRB. Please use ESRLBCND for all new designs.
Download PDF.
Related articles:
Downloads:
UL924 ESRLBCND and UL924 with two Control Units (03167-03)
This Diagram show connection of a sensor controlling each of the emergency and normal segments
of a fixture.
Download PDF.
Downloads:
UL924 ESRLBCND with Control Unit (03384-02)
This diagram shows a fixture with both emergency and normal segments being controlled via a single sensor, a single Control Unit (CU), and a single UL924 device.
Please note that the Control Unit's (CU) Load Limit, NEMA 410 Rating and 0-10 VDC Source/Sink limits cannot be exceeded when installing multiple drivers on a single Sensor/CU. CU Load limit is 5A, NEMA 410 rating for Peak Inrush current is 320A and the Source/Sink limit of the 0-10VDC Control wires is +/- 10mA.
Download PDF version of the line diagram.
Downloads:
UL924 LVS EPC-2-D-FM Fixture Mount, 120-277V, 0-10V Driver (03210-02)
The following line diagram shows the connections between a UL924 LVS (EPC-2-D-FM) Device with Fixture Mount Control Unit (CU-4E-FMH) that is 120-277 V and 0-10V Driver.
Download PDF.
Downloads:
UL924 LVS EPC-2-D-FM Nipple Mount, 120-277V, 0-10V Driver (03211-02)
The following line diagram shows the connections between a UL924 (EPC-2-D-FM) Device with Nipple Mount Control Unit (CU-4E-NME) and 0-10V Driver.
Download PDF.
Downloads:
ESR2401D Nipple Mount Relay, 120V only (02703-03)
Normal Emergency with UPS or Generator with one CU and Bypass Shunt Relay. Download PDF.
Downloads:
ESR2402D Nipple Mount Relay, 208-277V only (02702-03)
Normal Emergency with UPS or Generator with one CU and Bypass Shunt Relay. Download PDF.
Downloads:
ESRB Fixture Mount Relay, 120-277 V (02672-07)
The line diagram shows the connections between ESRB UL924 with Enlighted Control Unit (CU-4E).
Please note that the Control Unit's (CU) Load Limit, NEMA 410 Rating and 0-10 VDC Source/Sink limits cannot be exceeded when installing multiple drivers on a single Sensor/CU. CU Load limit is 5A, NEMA 410 rating for Peak Inrush current is 320A and the Source/Sink limit of the 0-10VDC Control wires is +/- 10mA.
Download the line diagram PDF.
Downloads:
ESRN Nipple Mount Relay 120-277V (02692-07)
The line diagram shows the connections between ESRN UL924 with Enlighted Control Unit (CU-4E).
Please note that the Control Unit's (CU) Load Limit, NEMA 410 Rating and 0-10 VDC Source/Sink limits cannot be exceeded when installing multiple drivers on a single Sensor/CU. CU Load limit is 5A, NEMA 410 rating for Peak Inrush current is 320A, and the Source/Sink limit of the 0-10VDC Control wires is +/- 10mA.
Download the line diagram PDF.
Downloads:
ESRN UL924 with Nipple Mount Control Unit & No Emergency Energy Metering (03204-04)
This diagram shows the connection between a fixture and both emergency and normal segments and this can be controlled via a single Sensor, single Control Unit (CU), and single UL924 device.
Download the line diagram PDF.
Downloads:
ESRN UL924 with Nipple Mount Control Unit (03383-02)
This diagram shows the connection between a fixture with an emergency driver and this can be controlled via a single sensor, single Control Unit (CU), and single UL924 device.
Download the line diagram PDF.
Downloads:
SU-5 Pendant Application with UL924 ESRN (02946-02)
Diagram depicts SU-5 Sensor and CU-4E Control Unit connected to an ESRN UL924 device for control of line dimmed emergency fixtures. Download PDF.
Downloads:
LVS-RRU-X-UNV-Fixture Mount-UL924 with Control Unit (03190-02)
The line diagram shows the connections between the Fixture Mount Control Unit (CU-4E), UL924 Device, and 0-10V driver.
Download the line diagram PDF.
Downloads:
RRU-X-UNV Fixture Mount Shunt Relay (02673-03)
The line diagram shows the connections between the Enlighted Control Unit (CU-4E) with UL924 Device and 0-10V driver.
Download the line diagram PDF.