Micro Sensor, 8-pin, (SU-5E)
Install Guide
Download the Micro Sensor, 8-pin, Installation Guide PDF: English rev.11 | German rev.07 | French rev.07 | Spanish 07
Overview
The Enlighted Micro Sensor, 8-pin, delivers all the functionality of our other sensors in a minimally sized package. The Micro Sensor, 8-pin, is designed to be easily mounted into lighting fixtures or ceiling tiles, such that only the discreet white faceplate is visible. The sensor slides into a carrier sleeve, fitting a standard 1/2 inch trade size knockout or 7/8 inch (22 mm) hole. Carrier sleeves compatible with either lighting fixtures or ceiling tiles are available. Sensor replacement requires no tools—simply slide the sensor out of the carrier, unplug the connector, and install the new sensor.
Micro Sensor and Carrier
The following sections describe installing the Micro sensor, 8-pin, in a fixture or tile.
If you have purchased the Hard Ceiling Mount Carrier (HCMC-SU-5E) as an optional component for installing the sensor, refer to the following articles:
Installation
Shipped Components: Enlighted Micro Sensor, 8-pin: SU-5E
Supplemental Components:
- Enlighted Sensor Cables:
- Female RJ45 coupler: CPL-RJ45
- 30-inch sensor cable for CU-4: CBL-5E-CU4-30N
- 7-foot sensor cable for CU-4: CBL-5E-CU4-7F
- 12-inch sensor cable for CU-4: CBL-5E-CU4-12N
- 30-inch Profile 0 Driver cable: CBL-5E-5W-30N
- Enlighted Control Unit: CU-4E-FM/FMH
- Tile Mount Carrier: TMC-SU-5E
- Hard Ceiling Mount Carrier: HCMC-SU-5E
Tools you may Need
- 7/8” Drill bit (1/2” knock out trade size)
- Hand drill
Caution
A qualified electrician must perform installation and maintenance per local, state, and national electrical codes (NEC) and requirements.
Installation Procedure
Before proceeding with the sensor installation, make sure to de-energize the luminaire.
Note: When replacing the white bezel with the black bezel, make sure the bezel is securely fastened in place so that the key is properly seated in the slot.
Fixture Mount Installation
Note: For fixture mounting, use the fixture carrier and nut that is shipped with the sensor. The fixture mount can accommodate up to 0.25” thickness materials.
Fixture Carrier and Nut
Step 1: De-energize the luminaire.
Step 2: Determine the sensor's location in the fixture and cut a ½ inch (7/8” diameter) knockout in the fixture.
Step 3: Insert the fixture carrier through the hole in the fixture.
Step 4: From behind the fixture, align the tabs of the nut with the keys on the fixture carrier.
Step 5: Slide the tabs of the nut along with the keys of the carrier to fasten the carrier.
Step 6: Insert the 8-pin end of the sensor cable through the carrier.
Step 7: Connect the 8-pin connector to the sensor.
Step 8: Guiding the wire from above, push the sensor into the carrier until it securely clicks into the carrier.
Step 9: Leave four inches of slack cable in the sequence loop to avoid pinching the cable and to bring the sensor down if it needs to be replaced.
Note: Do not pull the cable forcefully, as this might damage the cable or connector.
Step 10: See Connecting the Sensor Cable to the Control Unit.
Tile Mount Installation
Note: For tile mounting, the tile carrier and nut must be ordered separately. The tile mount can accommodate up to 1.5” thick tiles.
Tile Carrier and Nut
Step 1: De-energize the luminaire.
Step 2: Make a 7/8th diameter hole in the ceiling tile.
Step 3: Insert the tile carrier through the hole into the tile.
Step 4: Thread the plain end of the nut from behind the tile to secure the carrier.
If the tile is thicker than normal, flip the nut and thread the nut's ribbed end to secure the carrier.
Step 5: Insert the 8-pin end of the sensor cable through the carrier.
Step 6: Connect the 8-pin connector to the sensor.
Step 7: Guiding the wire from above, push the sensor into the carrier until it securely clicks into the carrier.
Step 8: Leave four inches of slack cable in the sequence loop to avoid pinching the cable and to bring the sensor down if it needs to be replaced.
Note: Do not pull the cable forcefully, as this might damage the cable or connector.
Step 9: See Connecting the Sensor Cable to the Control Unit.
Connecting the Sensor Cable to the Control Unit
Step 1: Connect one end of the sensor cable to the Control Unit (CU). For wiring connections from the Control Unit to the sensor, refer to the Control Unit Installation Guide.
Step 2: Energize the luminaire and confirm that the green LED is solid.
LED Description
LED Status | Description/Solution |
LED not on | The sensor is not powered on. Check power and wiring. |
Blinking Green | The commissioned sensor has powered up and has detected motion. If there is no motion in the sensor’s field of view, the blinking will stop. Wave your hands below the sensor to restart LED blinking. |
Solid Green | The uncommissioned sensor has powered up successfully and completed the wiring test with no unexpected conditions – waiting for discovery. |
Blinking Red | The uncommissioned sensor has powered up and completed the wiring test with one or more conditions unexpected of a typical LED fixture – waiting for discovery. |
Solid Red | Faulty sensor – replace the sensor. |
Solid Blue | The Sensor received a request to identify itself. |
Blinking Blue | The uncommissioned sensor powered up successfully, but the sensor is unable to detect an energy measurement device (CU or Driver), waiting for discovery. |
Interrupted Green | Un-commissioned fixtureless sensors. |
Product Compliance:
Model No: SU-5E-01
Product Code: SU-5e-xxx
xxx: IoT Note (IoT), Connected Lighting (CL), Independent Lighting/Enlighted One (IL)
FCC ID: AQQ-SU5E
IC: 10138A-SU5E
Rev.10
DoCs
Recommended articles:
- Micro Sensor, 8-pin, (SU-5E) Spec sheet
- Hard Ceiling Mount Carrier (HCMC-SU-5E) Spec Sheet
- Micro Sensor Tile Mount Carrier (TMC-SU-5E) Spec Sheet
- Gen 5 Sensor FAQs
Downloads:
Micro Sensor with 2-wire Adaptor (KIT-SU-5E-D)
Download the Micro Sensor with 2-wire adaptor Installation Guide PDF: English rev.07 | German rev.04 | French rev.04
Overview
The Enlighted Micro Sensor with 2-wire Adaptor delivers all the functionality of our other sensors in a minimally-sized package. It is designed to be easily mounted into lighting fixtures or ceiling tiles such that only the discreet white faceplate is visible. The sensor slides into a carrier sleeve, fitting a standard 1/2 inch trade size knockout or 7/8 inch (22 mm) hole. Carrier sleeves compatible with either lighting fixtures or ceiling tiles are available. Sensor replacement requires no tools—slide the sensor out of the carrier, unplug the connector, and install the new sensor.
Micro Sensor with 2-wire Adaptor Cable
The following sections describe installing the Micro sensor 2-Wire adaptor in a fixture or tile.
- Fixture Mount Sensor Installation
- Tile Mount Sensor Installation
- Connecting the Cable to the LED Driver
If you have purchased the Hard Ceiling Mount Carrier (HCMC-SU-5E) as an optional component for installing the sensor, refer to the following articles:
- Hard Ceiling Mount Carrier Spec Sheet
- Hard Ceiling Mount for Diffuser Fixture Mount for installation instructions.
Installation
Shipped Components
- Enlighted Micro Sensor
- Two-wire Adaptor Cable
Supplemental Components
- Tile Mount Carrier (TMC-SU-5E)*
- Hard Ceiling Mount Carrier (HCMC-SU-5E)*
- 18 AWG solid copper wire rated >=300v
Tools you may Need
- 7/8” Drill bit (1/2” knock out trade size)
- Hand drill
- Wire stripper
* Indicated products are sold separately. Contact Enlighted Customer Support.
Caution
A qualified electrician must perform the installation and maintenance under the local, state, and national electrical codes (NEC) and requirements.
Warning
- FELV circuits are not safe to touch.
- Isolate the circuits connected to any FELV source from the AC mains supply of the control gear.
- Ensure to protect the FELV circuit from any accidental contact.
- When installing the sensors, de-energize the FELV source and any AC main sources near the FELV.
- Place the sensors in a secure location, such as in the ceiling near a luminaire, with the cabling above the ceiling or within the luminaire.
- The NEC considers electrical equipment installed a minimum of 8 ft (2.5 m) off the floor to be suitably guarded against accidental contact.
- Circuits connected to any FELV control terminal must be insulated for the LV supply voltage of the control gear, and all terminals connected to the FELV circuit must be protected from accidental contact.
Fixture Mount Sensor Installation (Approved for Class 2, SELV and FELV Installations)
Note: For fixture mounting, use the fixture carrier and nut that is shipped with the sensor. The fixture mount can accommodate up to 0.25” (6.35 mm) thickness materials.
Fixture Carrier and Nut
Step 1: De-energize the luminaire.
Step 2: Determine the sensor's location in the fixture and cut a ½ inch (7/8” or 23 mm diameter) knockout in the fixture.
Step 3: Insert the fixture carrier through the hole in the fixture.
Step 4: From behind the fixture, align the tabs of the nut with the keys on the fixture carrier.
Step 5: Slide the tabs of the nut along with the keys of the carrier to fasten the carrier.
Step 6: Connect the adaptor cable to the sensor.
Step 7: Cut two lengths of 18 AWG (0.75 mm2) solid wire of the required length. Strip each end of the two wires leaving 5/16" (8 mm) of exposed wire.
Step 8: Insert one end of the pair of wires through the hole in the fixture and connect the wires to the sensor.
Step 9: Guiding the wire from above, push the sensor into the carrier until it securely clicks into the carrier.
Step 10: Leave four inches of slack cable in the sequence loop to avoid pinching the cable and bring the sensor down if it needs to be replaced.
Note: Do not pull the cable forcefully, as this might damage the cable or connector.
Step 11: See section Connecting the Cable to the LED Driver.
Tile Mount Sensor Installation (Approved for Class 2, SELV and NOT approved for FELV Installations)
Note: For tile mounting, the tile carrier and nut must be ordered separately. The tile mount can accommodate up to 1.5” (38 mm) thick tiles.
Tile Carrier and Nut
Step 1: De-energize the luminaire.
Step 2: Make a 7/8" or 23 mm diameter hole in the ceiling tile.
Step 3: Insert the tile carrier through the hole into the tile.
Step 4: Thread the plain end of the nut from behind the tile to secure the carrier.
If the tile is thicker than normal, flip the nut and thread the nut's ribbed end to secure the carrier.
Step 5: Insert the adaptor cable into the sensor.
Step 6: Cut two lengths of 18 AWG (0.75 mm2) solid wire of the required length. Strip each end of the two wires leaving 5/16" (8 mm) of exposed wire.
Step 7: Insert one end of the wires through the hole in the tile and connect the wires to the sensor.
Step 8: Guiding the wire from above, push the sensor into the carrier until it securely clicks into the carrier.
Step 9: Leave four inches of slack cable in the sequence loop to avoid pinching the cable and bring the sensor down if it needs to be replaced.
Note: Do not pull the cable forcefully, as this might damage the cable or connector.
Step 10: See section Connecting the Cable to the LED Driver.
Connecting the Cable to the LED Driver
Step 1: Connect the other end of the pair of wires to the LED Driver.
Step 2: Turn the power on by switching on the circuit breaker and wait for the green LED to appear.
LED Description
LED Status | Description/Solution |
LED not on | The sensor is not powered on.Check power and wiring. |
Blinking Green | The commissioned sensor has powered up and has detected motion. If there is no motion in the sensor’s field of view, the blinking will stop. Wave your hands below the sensor to restart LED blinking. |
Solid Green | The uncommissioned sensor has powered up successfully and completed the wiring test with no unexpected conditions – waiting for discovery. |
Blinking Red | The uncommissioned sensor has powered up and completed the wiring test with one or more conditions unexpected of a typical LED fixture – waiting for discovery. |
Solid Red | Faulty sensor – replace the sensor. |
Solid Blue | The sensor received a request to identify itself. |
Blinking Blue | The uncommissioned sensor powered up successfully, but the sensor is unable to detect an energy measurement device (CU or Driver), waiting for discovery. |
Blinking Magenta | When the sensor is connected to a DALI emergency driver that is currently in the process of an emergency test or an emergency test pending. |
Interrupted Green | Un-commissioned fixtureless sensors. |
Product Compliance
Model No: SU-5E-01
Product Code: KIT-SU-5E-D-xxx
xxx: IoT Note (IoT), Connected Lighting (CL)
FCC ID: AQQ-SU5E
IC: 10138A-SU5E
Rev.07
DoCs
Recommended articles:
Downloads:
Low Bay Ruggedized Micro Sensor, 8-pin, (SU-5E-LR)
Download the Low Bay Ruggedized Micro Sensor, Installation Guide PDF: English rev.04
Overview
The Low Bay Ruggedized Micro Sensor, 8-pin, is designed for outdoor applications, parking structures, and damp or wet locations that require a sensor with an IP65 rating. The sensor can be easily mounted into lighting fixtures or standard 1/2" EMT threaded couplers and fittings such that only the discreet faceplate is visible. The sensor threads into an industry standard ½"-13 threaded mounting hole.
The following sections describe installing the Low Bay Ruggedized Micro sensor, 8-pin, in a fixture or sheet.
- Fixture Mount Sensor Installation
- Sheet Metal Sensor Installation
- Connecting the Sensor Cable to the Control Unit
Installation Procedure
Shipped Components
- Low Bay Ruggedized Micro Sensor (SU-5E-LR)
Supplemental Components
- Enlighted Sensor Cable
- Enlighted Control Unit
Tools you will Need
- Locknut (Optional)
- Flat blade screwdriver
Caution: Installation and maintenance must be performed by a qualified electrician in accordance with local, state, and national electrical codes (NEC) and requirements. DO NOT use an HCMC to mount the sensor to a ceiling tile. The sensor needs to be secured with
a locknut.
DO NOT mount the sensor if the mounting accessory has the following defects:
- The knockout hole has a ridge inside that prevents the sensor from going all the way
- The mounting accessory faceplate does not have a large flat surface area for the sensor to fit snugly mounted.
- The sensor lens protrudes out and does not fit securely into the knockout hole.
- A gap exists between the washer and the surface of the mounting accessory.
WARNING: When the sensors are installed incorrectly, it can cause water leakage, electrical shock,
and the unit to fail.
Before proceeding with the sensor installation, make sure to de-energize the luminaire.
Note: The black bezel will be attached with the O-ring in place when you receive it. When using the white bezel, make sure that the O-ring is in place under the bezel.
Fixture Mount Sensor Installation
Step 1: Identify an outdoor fixture that has an industry-standard ½” (12.7 mm) -13 threaded mounting hole to which the sensor is to be mounted.
Step 2: Insert the sensor through the mounting hole and thread the sensor until the washer makes contact with the fixture surface.
Step 3: Continue to tighten the sensor with a ¼ turn to make sure that the sensor fits in snugly to prevent water leakage.
Sheet Metal Sensor Installation
Note: For sheet metal mounting, the ½” Lock nut must be ordered separately.
Step 1: Drill a 7/8" (22mm) knock-out hole in the sheet metal.
Step 2: Insert the sensor through the knock-out hole with the lens facing down.
Step 3: Thread the locknut tightly from behind the sheet metal to secure the sensor to prevent water leakage.
Connecting the Sensor Cable to the Control Unit
Step 1: Connect one end of the sensor cable to the Control Unit (CU). For wiring connections from the Control Unit to the sensor, refer to the Control Unit Installation Guide.
Step 2: Energize the luminaire and confirm that the green LED is on solid.
LED Description
LED Status | Description/Solution |
LED not on | The sensor is not powered on.Check power andwiring. |
Blinking Green | The commissioned sensor has powered up and has detected motion. If there is no motion in the sensor’s field of view, the blinking will stop. Wave your hands below the sensor to restart LED blinking. |
Solid Green | The uncommissioned sensor has powered up successfully and completed the wiring test with no unexpected conditions – waiting for discovery. |
Blinking Red | The uncommissioned sensor has powered up and completed the wiring test with one or more conditions unexpected of a typical LED fixture – waiting for discovery. |
Solid Red | Faulty sensor – replace the sensor. |
Solid Blue | The Sensor received a request to identify itself. |
Blinking Blue | The uncommissioned sensor powered up successfully, but the sensor is unable to detect an energy measurement device (CU or Driver), waiting for discovery. |
Interrupted Green | Un-commissioned fixtureless sensors. |
Product Compliance:
Model No: SU-5E-LR
Product Code: SU-5e-xxx
FCC ID: AQQ-SU5E
IC: 10138A-SU5E
Rev.04
DoCs
Recommended articles:
Downloads:
High Bay Sensor, 8-pin, (SU-5S-H)
Download the Highbay Sensor, 8-pin, Installation Guide PDF: English rev.07 | German rev.05 | French rev.05
Overview
The Enlighted High Bay Sensor, 8-pin, is designed for indoor applications with high ceilings such as warehouses, atriums, and manufacturing facilities. The High Bay Sensor, 8-pin, comes with a nylon threaded screw for mounting in acoustical tile or drywall ceilings. Pendant button mount and flat metal bracket mount options are available separately.
High Bay Sensor, 8-pin, (Front and Rear)
Installation
Shipped Components:
- High Bay Sensor, 8-pin: SU-5S-H
- Anchor Screw: BTTN-SU-2-00
Supplemental Components:
- Enlighted Sensor Cables:
- Female RJ45 Coupler: CPL-RJ45
- 7-foot sensor cable for CU-4: CBL-RJ45-RJ45-7F
- 7-foot Profile 0 Driver cable: CBL-RJ45-5W-7F
- Enlighted Control Unit: CU-4E-FM/FMH
- Adjustable Mounting Bracket: BRKT-SU-2-00
Caution
A qualified electrician must perform installation and maintenance per local, state, and national electrical codes (NEC) and requirements.
Procedure:
The High Bay Sensor, 8-pin, can be mounted to ceiling tiles using an anchor screw or pendant and industrial fixtures using the adjustable mounting bracket.
Step 1: De-energize the luminaire.
Step 2: Mount the Control Unit (CU) in a UL-approved enclosure. Refer to the Control Unit Installation Guide for installation and wiring instructions. The sensor cable from the CU terminating in an RJ45 connector must be connected to the sensor.
Mounting using an Anchor Screw (BTTN-SU-2-00)
The sensor (SU-5S) should be mounted to the ceiling tile within a few inches (between 1 ¾” to 3”) of the lighting fixture.
Step 1: Determine the location of the sensor. Push and rotate the anchor screw to the tile at that location.
Step 2: Select a place near the anchor screw for the RJ45 connector of the sensor cable from the CU to exit. Make a small cut in the ceiling tile for the cable to exit.
Step 3: Connect the sensor cable’s RJ45 connector to the sensor bottom.
Step 4: Align the anchor screw with the slot provided on the sensor bottom. Slide the sensor onto the screw head.
Step 5: Slip the excess sensor cable up into the plenum area and adjust the ceiling tile to the original position.
Step 6: Energize the luminaire and confirm that the green LED is solid.
Mounting using Adjustable Mounting Bracket (BRKT-SU-2-00)
The sensor (SU-5S-H) can be mounted to a pendant and industrial fixtures using the mounting bracket. The galvanized steel mounting bracket width is 1.35".
Step 1: Determine the mounting location of the sensor on the fixture. To ensure that the fixture does not block the sensor view, level the sensor to the bottom of the fixture and provide enough clearance from the fixture. See the examples below.
Step 2: Bend the adjustable mounting bracket to the required shape. Fasten the bracket to the fixture using two 8” screws.
Step 3: Connect the sensor cable’s RJ45 connector from the CU to the bottom of the sensor.
Step 4: Slide the sensor onto the head of the mounting bracket.
Step 5: Secure the sensor cable to the bracket or fixture using cable ties, electrical tape, clips, etc., as appropriate for the installation.
Step 6: Energize the luminaire and confirm that the green LED is solid.
LED Description
LED Status | Description/Solution |
LED not on | The sensor is not powered on.Check power andwiring. |
Blinking Green | The commissioned sensor has powered up and has detected motion. If there is no motion in the sensor’s field of view, the blinking will stop. Wave your hands below the sensor to restart LED blinking. |
Solid Green | The uncommissioned sensor has powered up successfully and completed the wiring test with no unexpected conditions – waiting for discovery. |
Blinking Red | The uncommissioned sensor has powered up and completed the wiring test with one or more conditions unexpected of a typical LED fixture – waiting for discovery. |
Solid Red | Faulty sensor – replace the sensor. |
Solid Blue | The Sensor received a request to identify itself. |
Blinking Blue | The uncommissioned sensor powered up successfully, but the sensor is unable to detect an energy measurement device (CU or Driver), waiting for discovery. |
Interrupted Green | Un-commissioned fixtureless sensors. |
Product Compliance

Model No: SU-5S-H: High Bay Sensor, 8-pin
Product Code: SU-5S-H-xxx
xxx: IoT Node (IoT), Connected Lighting (CL),
Independent Lighting/Enlighted One (IL)
FCC ID: AQQ-SU5S
IC: 10138A-SU5S
Rev.07
DoCs
Recommended article:
Downloads:
High Bay Sensor, 2-wire, (SU-5S-2W-H)
Download the Highbay Sensor, 2- wire, Installation Guide PDF: English rev.09 | German rev.05 | French rev.05
Overview
The High Bay Sensor, 2-wire, is a complete sensing and lighting control node powered from its attached light fixture. Sensor information combined with a configurable behavior profile makes the High Bay Sensor, 2-wire, an integral component of intelligent lighting control and sensing solution. With integrated wireless communications for data transmission and remote configuration as well as autonomous fixture-level control, this sensor brings advanced lighting automation to a whole new level.
Installation
Shipped Components
- High Bay Sensor, 2-wire, (SU-5S-2W-H), or Fixtureless (SU-5S-2W-H-FL)
- Anchor Screw: BTTN-SU-2-00
Supplemental Components
- Adjustable Mounting Bracket: BRKT-SU-2-00
Tools you may Need
- Wire Stripper
Caution
A qualified electrician must perform installation and maintenance under local, state, and national electrical codes (NEC) and requirements.
Warning
- FELV circuits are not safe to touch.
- Isolate the circuits connected to any FELV source from the AC mains supply of the control gear.
- Ensure to protect the FELV circuit from any accidental contact.
- When installing the sensors, de-energize the FELV source and any AC main sources near the FELV.
- Place the sensors in a secure location, such as in the ceiling near a luminaire, with the cabling above the ceiling or within the luminaire.
- The NEC considers electrical equipment installed a minimum of 8 ft (2.5 m) off the floor to be suitably guarded against accidental contact.
- Circuits connected to any FELV control terminal must be insulated for the LV supply voltage of the control gear, and all terminals connected to the FELV circuit must be protected from accidental contact.
Mounting using an Anchor Screw (BTTN-SU-2-00)
The High Bay Sensor, 2-wire, can be mounted to ceiling tiles using an anchor screw or pendant and industrial fixtures using the adjustable mounting bracket.
Step 1: De-energize the luminaire.
Mounting using an Anchor Screw
The High Bay sensor, 2-wire, should be mounted to the ceiling tile as close as possible to the lighting fixture.
Step 1: Determine the location of the sensor. Push and rotate the anchor screw to the tile at that location.
Step 3: See section Connecting the Sensor Cable to the LED Driver before proceeding further.
Step 4: Select a place near the anchor screw for the pair of wires from the LED driver to exit. Make a small cut in the ceiling tile for the wire to exit.
Step 5: Connect the other end of the wires to the push in connector seen at the bottom of the mounting sensor using an anchor screw.
Step 6: Align the anchor screw with the slot provided on the sensor bottom. Slide the sensor onto the screw head.
Step 7: Slip the excess sensor wire into the plenum area and adjust the ceiling tile to the original position.
Step 8: Energize the luminaire and confirm that the green LED is solid.
Mounting using Adjustable Mounting Bracket (BRKT-SU-2-00)
The sensor can be mounted to the pendant and industrial fixtures using the mounting bracket. The galvanized steel mounting bracket width is 1.35".
Step 1: Determine the mounting location of the sensor on the fixture. To ensure that the fixture does not obstruct the sensor's view, level the sensor to the fixture's bottom and provide enough clearance from the fixture. See the examples below.
Step 2: Bend the adjustable mounting bracket to the required shape. Fasten the bracket to the fixture using two #8 screws (5/32 of an inch or 0.16″ in thread diameter or 4 mm thread diameter).
Step 3: See section Connecting the Sensor Cable to the LED Driver before proceeding further.
Step 4: Connect the other end of the pair of wires from the LED driver to the bottom of the sensor.
Step 5: Slide the sensor onto the head of the mounting bracket.
Step 6: Secure the sensor cable to the bracket or fixture using cable ties, electrical tape, clips, etc., as appropriate for the installation.
Step 7: Energize the luminaire and confirm that the green LED is solid.
Connecting the Cable to the LED Driver
Step 1: Measure the distance between the sensor’s installation location and the LED driver.
Step 2: Cut two lengths of 18 AWG (0.75 mm2) solid wire of the required length. Strip each end of the two wires leaving 5/16 inch (7.95 mm) of exposed wire.
Step 3: Connect the end of the pair of wires to the LED Driver.
LED Description
LED Status | Description/Solution |
LED not on | The sensor is not powered on. Check power and wiring. |
Blinking Green | The commissioned sensor has powered up and has detected motion. If there is no motion in the sensor’s field of view, the blinking will stop. Wave your hands below the sensor to restart LED blinking. |
Solid Green | The uncommissioned sensor has powered up successfully and completed the wiring test with no unexpected conditions – waiting for discovery. |
Blinking Red | The uncommissioned sensor has powered up and completed the wiring test with one or more conditions unexpected of a typical LED fixture – waiting for discovery. |
Solid Red | Faulty sensor – replace the sensor. |
Solid Blue | The sensor received a request to identify itself. |
Blinking Blue | The uncommissioned sensor powered up successfully, but the sensor is unable to detect an energy measurement device (CU or Driver), waiting for discovery. |
Blinking Magenta | When the sensor is connected to a DALI emergency driver that is currently intheprocessofan emergency testoran emergency test pending. |
Interrupted Green | Un-commissioned fixtureless sensors. |
Product Compliance
Model No:
SU-5S-2W-H: High Bay Sensor, 2-wire
Product Code: SU-5S-2W-H-xxx/SU-5S-2W-H-xxx-FL
xxx: IoT Node (IoT), Connected Lighting (CL)
FL: Fixtureless
FCC ID: AQQ-SU5S
IC: 10138A-SU5S
Rev.09
DoCs
Recommended articles
- High Bay Sensor, 2-wire, (SU-5S-2W-H) Spec Sheet
- 2-wire, Install Solutions for Fixtureless Sensors
- High Bay Sensor FAQs
Downloads:
Ruggedized Sensor, 8-pin, (SU-5S-xRx)
Download the Ruggedized Sensor, 8-pin, Installation Guide PDF: English rev.08 | German rev.06 | French rev.06
Overview
The Enlighted Ruggedized Sensor, 8-pin, is designed for outdoor applications, parking structures, and damp or wet locations that require a sensor with an IP65 rating. The Ruggedized Sensor installs into a standard 1/2 inch fixture knockout. A permanently attached 22-inch cable with an RJ-45 connector must be fed through the opening before the sensor is secured via a threaded locknut provided with the sensor.
Ruggedized Sensor (Front and Rear)
Installation
If you have ordered the Hard Ceiling Mount Carrier (HCMC-SU-5E) as an optional component to install the Ruggedized sensor, refer to the following articles:
The following components are shipped with the Ruggedized sensor.
Shipped Components:
- Enlighted Ruggedized Sensor, 8-pin: SU-5S-HRW/LRW
- ½ inch Lock Nut
Supplemental Components:
- ½ inch LB Conduit Body
- ½ inch Chase Nipple
- Enlighted Control Unit: CU-4E-FM/FMH
- Enlighted Sensor Cable:
- Female RJ45 coupler: CPL-RJ45
- 7-foot Sensor able for CU-4 and IoT ReadyTM drivers: CBL-RJ45-RJ45-7F
- 7-foot Profile 0 Driver cable: CBL-RJ45-5W-7F
- Cable Coupler: CPL-RJ45
- Hard Ceiling Mount Carrier: HCMC-SU-5E
Tools you may Need
- ½ inch Knock out tool
Caution
A qualified electrician must perform installation and maintenance per local, state, and national electrical codes (NEC) and requirements.
Procedure
The Ruggedized sensor, 8-pin, is shipped with the cable attached to the sensor. The sensor can be mounted to the fixture using a conduit body and chase nipple or locknut.
Step 1: De-energize the luminaire.
Mounting using the Conduit Body and Chase Nipple
Step 1: Remove the cover plate of the ½ inch LB conduit body by removing the two screws.
Step 2: Thread the Ruggedized sensor onto the LB conduit body.
Step 3: Replace the cover and two screws on the LB conduit body.
Step 4: Knock out a ½ inch hole on the end of the light fixture.
Step 5: Mount the Ruggedized Sensor LB Conduit to the fixture by guiding the sensor cable through the knockout and chase nipple into the fixture.
Step 6: Thread the chase nipple to connect the LB conduit to the fixture securely.
Mounting using the Locknut
Step 1: Knock out a ½ inch hole on the bottom of the light fixture.
Step 2: Glide the sensor cable through the knockout of the fixture.
Step 3: Thread the locknut tightly to secure the sensor to the fixture.
Connecting the Sensor Cable to the Control Unit
Step 1: Use an RJ45 coupler with an Enlighted Sensor cable to connect the RJ45 end of the sensor cable to the Control Unit's connector (CU).
For wiring connections from the Control Unit to the sensor, refer to the Control Unit Installation Guide.
Step 2: Energize the luminaire and confirm that the green LED is solid.
LED Description
LED Status | Description/Solution |
LED not on | The sensor is not powered on.Check power andwiring. |
Blinking Green | The commissioned sensor has powered up and has detected motion. If there is no motion in the sensor’s field of view, the blinking will stop. Wave your hands below the sensor to restart LED blinking. |
Solid Green | The uncommissioned sensor has powered up successfully and completed the wiring test with no unexpected conditions –waiting for discovery. |
Blinking Red | The uncommissioned sensor has powered up and completed the wiring test with one or more conditions unexpected of a typical LED fixture – waiting for discovery. |
Solid Red | Faulty sensor – replace the sensor. |
Solid Blue | The Sensor received a request to identify itself. |
Blinking Blue | The uncommissioned sensor powered up successfully, but the sensor is unable to detect an energy measurement device (CU or Driver), waiting for discovery. |
Interrupted Green | Un-commissioned fixtureless sensors. |
Product Compliance:
Models:
SU-5S-HRW: High Bay, White, Ruggedized Sensor
SU-5S-LRW: Standard Bay, White, Ruggedized Sensor
Product Codes:
SU-5S-xRx-xxx
xRx: HRW, LRW
xxx: IoT Node (IoT), Connected Lighting (CL), Independent Lighting/Enlighted One (IL)
FCC ID: AQQ-SU5S
IC: 10138A-SU5S
Rev: 08
DoCs
Recommended articles:
- Ruggedized Sensor, 8-pin, (SU-5S-xRx) Spec Sheet
- Hard Ceiling Mount Carrier (HCMC-SU-5E) Spec Sheet
- Hard Ceiling Mount for Diffuser Fixture Mount
Downloads:
Ruggedized Sensor, 2-wire, (SU-5S-2W-xRx)
Download the Ruggedized Sensor, 2-wire, Installation Guide PDF: English rev.08 | German rev.05 | French rev.05
Overview
The Ruggedized Sensor, 2-wire, is a complete sensing and lighting control node powered from its attached light fixture.
Ruggedized Sensor, 2-wire, (Front and Rear)
Installation
Shipped Components
- Enlighted Ruggedized Sensor, 2-wire: SU-5S-2W-xRx (HRW/LRW), or
Fixtureless: (SU-5S-2W-HRW/LRW-FL) - ½ (13 mm) inch Lock Nut
Supplemental Components
- ½ (13 mm) inch LB Conduit Body
- ½ (13 mm) inch Chase Nipple
- Hard Ceiling Mount Carrier: HCMC-SU-5E
Tools you may Need
- ½ (13 mm) inch Knock out tool
- Wire Stripper
Caution
A qualified electrician must perform installation and maintenance per local, state, and national electrical codes (NEC) and requirements.
Warning
- FELV circuits are not safe to touch.
- Isolate the circuits connected to any FELV source from the AC mains supply of the control gear.
- Ensure to protect the FELV circuit from any accidental contact.
- When installing the sensors, de-energize the FELV source and any AC main sources near the FELV.
- Place the sensors in a secure location, such as in the ceiling near a luminaire, with the cabling above the ceiling or within the luminaire.
- The NEC considers electrical equipment installed a minimum of 8 ft (2.5 m) off the floor to be suitably guarded against accidental contact.
- Circuits connected to any FELV control terminal must be insulated for the LV supply voltage of the control gear, and all terminals connected to the FELV circuit must be protected from accidental contact.
Ruggedized Sensor Installation
The Ruggedized sensor, 2-wire, is shipped with the cable attached to the sensor. The cable connection is compatible with 18AWG (0.75 mm2) solid wires with 7-9 mm (0.28-0.35 inches) of stripped length. The sensor can be mounted to the fixture using a conduit body and chase nipple or locknut. If you have ordered the Hard Ceiling Mount Carrier as an optional component, refer to the Hard Ceiling Mount for Diffuser Fixture Mount installation.
Step 1: De-energize the luminaire.
Mounting using the Conduit Body and Chase Nipple
Step 2: Remove the cover plate of the ½ inch (13 mm) LB conduit body by removing the two screws.
Step 2: Thread the Ruggedized sensor onto the LB conduit body.
Step 3: Replace the cover and two screws on the LB conduit body.
Step 4: Knock out a ½ inch (13 mm) hole on the end of the light fixture.
Step 5: Mount the Ruggedized Sensor, 2-wire, LB conduit to the fixture by guiding the sensor cable through the knockout and chase nipple into the fixture.
Step 6: Thread the chase nipple to securely connect the LB conduit to the fixture.
Mounting using the Locknut
Step 1: Knock out a ½ inch (13 mm) hole on the bottom of the light fixture.
Step 2: Glide the sensor cable through the knockout of the fixture.
Step 3: Thread the locknut tightly to secure the sensor to the fixture.
Connecting the Sensor Cable to the LED Driver
Step 1: Insert the end of the pair of wires into the LED driver.
Step 2: Energize the luminaire and confirm that the green LED is solid. Refer to the LED Descriptions.
LED Description
LED Status | Description/Solution |
LED not on | The sensor is not powered on.Check power and wiring. |
Blinking Green | The commissioned sensor has powered up and has detected motion. If there is no motion in the sensor’s field of view, the blinking will stop. Wave your hands below the sensor to restart LED blinking. |
Solid Green | The uncommissioned sensor has powered up successfully and completed the wiring test with no unexpected conditions – waiting for discovery. |
Blinking Red | The uncommissioned sensor has powered up and completed the wiring test with one or more conditions unexpected of a typical LED fixture – waiting for discovery. |
Solid Red | Faulty sensor – replace the sensor. |
Solid Blue | The sensor received a request to identify itself. |
Blinking Blue | The uncommissioned sensor powered up successfully, but the sensor is unable to detect an energy measurement device (CU or Driver), waiting for discovery. |
Blinking Magenta | When the sensor is connected to a DALI emergency driver that is currently in the process of an emergency test or an emergency test pending. |
Interrupted Green | Un-commissioned fixtureless sensors. |
Product Compliance:
Model No:
SU-5S-2W-HRW: Ruggedized Sensor, 2-wire, High Bay, White
SU-5S-2W-LRW: Ruggedized Sensor, 2-wire, Standard, White
Product Code: SU-5S-2W-xRx-xxx
xRx: HRW, LRW xxx: IoT Node (IoT), Connected Lighting (CL)
xRx-FL: HRW, LRW, Fixtureless (FL)
FCC ID: AQQ-SU5S
IC: 10138A-SU5S
Rev: 08
DoCs
Recommended articles:
Downloads:
Surface Sensor, USB, (SU-5i-USB)
Download the Surface Sensor, USB, Installation Guide PDF: English rev.07 | German rev.06 | French rev.06
Before you install the Surface Sensor, please read the guidelines for designing and deploying solutions with Enlighted Surface Sensor (SU-5i-USB).
Overview
The Surface Sensor, USB, available in a minimally-sized package, provides users with real-time occupancy availability. The Surface Sensor, optimized for easy deployment, mounts to ceiling tiles and under desks. An innovative mount-based design or an adhesive strip included in the kit supports easy installation and maintenance.
Shipped Components
- Surface Sensor, USB, (SU-5i-USB)
- One VHB adhesive strip
Optional Components
- Mount bracket* with two #4 0.5” wood screws (BRKT-SU5i-50)
*50-pack of the brackets with screws sold separately with the optional mount bracket. Contact Enlighted Support.
Items you may Need
- USB-A to micro USB-B or micro USB-A connector cable up to 8m or 26.2 feet in length
- AC/DC 5V with 10W or 3W external wall mounted power adapter.
- Cable clips with strong adhesive tape.
Tools you may Need
- Hand screwdriver
Caution
- Installation and maintenance must be per local, state, and national electrical codes (NEC) and requirements.
- One end of the cable connects to the sensor's USB port, and the other end into a power adaptor.
- Power the sensor to an uncontrolled receptacle that continuously supplies power. Do not connect it to a controlled receptacle that provides power only when needed.
Guidelines:
- Center and mount the sensor to the underside of the desk 15-26” from the front edge of the desk and at least 5” from the rear edge for a typical 27” height seated desk or a 42-50” height standing desk.
- Mount the sensor parallel to the front edge of the desk.
- After installation, the sensor lens must be facing the desk occupant for the sensor to detect occupancy.
- Ensure that the USB cable is long enough to plug it into the nearest USB adaptor.
Installation
The Surface Sensor can be installed under the desk. The Surface sensors are shipped with the adhesive strip. The mounting bracket must be ordered separately.
The sensors can be installed using:
Since desks can be of wood or metal, use either adhesive strip or wood screws to mount the sensor to the underside of the desk.
Installing the sensor with an adhesive strip is faster, and it works with almost any surface. For a long-lasting bond, use the adhesive tape without the mount. However, it may be difficult to remove the sensor later. Also, note that removing the adhesive strip from painted surfaces can leave marks.
Installing the sensor using wood screws can take longer, but it is easier to remove the sensor when needed.
Using Adhesive Strip
Step 1: Use a dry clean cloth or paper towel to clean the desk's underside surface to ensure a strong bond.
Step 2: Remove the plastic strip on the double-sided adhesive strip and fix it to the back of the sensor.
Step 3: For ceiling applications, remove the mask over the lens. Hold the top edge of the dome-shaped mask, rotate it counterclockwise, and lift the mask.
Step 4: Peel the backing from the other side of the adhesive.
Step 5: For ceilings, hold the sensor firmly for five seconds to ensure proper adhesion to the surface.
For desks, hold the sensor such that the USB port faces the rear of the desk, and the sensor lens is facing the desk occupant. Then, firmly press the sensor into the underside of the desk.
Step 6: Allow at least 30 minutes for the mount to adhere to the surface.
Using Wood Screws (for Desk)
Step 1: Insert the wood screws through the mounting holes with the tab facing the desk's front edge. Fasten the mount to the underside of the desk using a screwdriver.
Step 2: When placing the sensor inside the mount, hold the sensor with the USB port facing the rear of the desk.
Step 3: Place the sensor by guiding the grooves in the base onto the hooks on the mount. Slide the sensor back until you hear a click to secure it to the mount.
Wiring the Cable to the Power Supply
Connect the USB end of the sensor cable into the micro USB port on the sensor and the other end to a powered USB external adaptor plugged into the wall. Power the Surface Sensor to an uncontrolled receptacle that continuously supplies power. Do not connect it to a controlled receptacle.
Confirm that the green LED is solid. A red solid or blinking LED indicates a faulty sensor or wiring issue.
To keep cables organized, use a cable holder with cord clips for holding the extra length of the cable. Ceiling sensors can use up to 8m extended cable.
Removing the Sensor
If you have used adhesive tape, peel off the tape by pulling up each corner and peeling it to the center. You can try rubbing some alcohol into the adhesive to loosen it if it is too sticky. Gently remove the sensor from the desk.
If you have used wood screws, insert a flat-head screwdriver between the tab on the mount and the sensor. Press the tab up and gently remove the sensor by sliding it forward and down from the mount.
LED Description
LED Status | Description/Solution |
LED not on | Power issue or faulty sensor. Check power and wiring. |
Blinking Green | The commissioned sensor has powered up and has detected motion. If there is no motion in the sensor’s field of view, the blinking will stop. Wave your hands below the sensor to restart LED blinking. |
Solid Green | The un-commissioned sensor has powered up successfully and waiting for discovery. |
Solid Red | Faulty sensor –replace the sensor. |
Solid Blue | The sensor received a request to identify itself. |
Product Compliance
Model No: SU-5i-USB
Product Code: SU-5i-xxx
xxx: IoT Note (IoT)
FCC ID: AQQ-SU5I
IC: 10138A-SU5I
Rev.06
DoCs: enlightedinc.com/eu-docs/
FCC and Industry Canada Compliance Information This equipment has been tested and found to comply with Class A digital device limits, pursuant to part 15 of the FCC Rules. These limits are designed This device complies with Part 15 of the FCC Rules and Industry Canada license-exempt RSS standard(s). Operation is subject to the following three conditions:
Changes or modifications not expressly approved by Enlighted Inc. could void the user's authority to operate the equipment. Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence. L'exploitation est autorisée aux deux conditions suivantes:
CE This device complies with the essential requirements and other relevant requirements of the R&TTE Directive (1999/5/EC) and Radio Equipment Directive (RED) 2014/53/EU. The equipment is Class 1 radio equipment that can be placed on the market and put into service without restrictions according to Article 1(3) of Commission Decision 2000/299/EC (Version July 2014). Wireless protocol: IEEE802.15.4, Radio Freq: 2400 – 2483.5MHz, RF TX output power (max): 3dBm |
Recommended articles:
Downloads:
Micro Sensor Mounting Case (CASE-SU-5E)
Download the Micro Sensor, Mounting Case, Installation Guide PDF: English rev.03 | German rev.03 | French rev.03
Overview
The Enlighted Mounting Case (CASE-SU-5E) provides a flexible solution for mounting the SU-5E Micro sensor on a variety of surfaces either attached directly to or separate from a lighting fixture. Easy to install, the case securely supports the sensor and routes the sensor cable through the back or side of the case. After the bracket is mounted, the case can be easily rotated to adjust the sensor’s field of view.
SU-5E Mounting Case
Installation
Shipped Components:
- SU-5E Sensor Carrier
- SU-5E Mounting Bracket
- ½ inch Chase Nipple and Locknut
- 2 nos. #8 Anchor Screws (Drywall® mount)
- 2 nos. #8 Metal Self-tapping Screws (Fixture mount)
Supplemental Components:
- 400BAC Wiremold® Conduit
- 18” AWG Cable
- 30-inch Sensor cable for CU-4 and IoT ReadyTM drivers: CBL-5E-CU4-30N
- 7-foot Sensor cable for CU-4 and IoT ReadyTM drivers: CBL-5E-CU4-7F
Tools you may Need
- ½” knockout set
- Hand drill
- Wire stripper
- Pliers
- Phillips screwdriver
Caution
Installation and maintenance must be performed by a qualified electrician in accordance with local, state, and national electrical codes (NEC) and requirements.
The circuit breaker must be switched off to turn the power off to the light fixture.
Mounting with the Bracket
You can mount the Microsensor to fixtures with a knockout or to sheetrock and fixtures without a knockout.
Option 1: Fixtures with Knockout
Step 1: Connect the 8-pin end of the sensor cable to the sensor.
Step 2: Guide the sensor cable wire through the front and back holes in the sensor carrier. Pull the cable gently until the sensor lens clicks securely into the carrier.
Step 3: Remove the ½” fixture knockout.
Step 4: Insert ½” Chase Nipple to the inside of the bracket.
Step 5: Connect the bracket to the fixture by threading the locknut screw to the Chase Nipple.
Step 6: Align the sensor lens with the curved edge of the bracket, insert the sensor cable through the Chase Nipple into the fixture.
Note: Only when the sensor lens is aligned with the curved edge of the bracket, the sensor can rotate freely to the desired angle within the bracket.
Step 7: Insert the sensor cable through the Chase Nipple into the fixture, and slide the sensor carrier until it clicks into the mounting bracket.
Option 2: Sheetrock and Fixtures without Knockout
Step 1: Locate the tab on the side of the mounting bracket and break away the tab.
Step 2: Mount the bracket to the fixture or drywall. For fixtures, use the metal-self tapping screws. For drywall, use anchor screws
Step 3: Insert the carrier with the sensor into the bracket. Make sure the sensor wires exit through the open slot in the bracket.
Step 4: only for drywall - Insert the cable through the Wiremold conduit.
Rotating the Sensor
After mounting with the bracket, rotate the sensor to the required direction.
Mounting Without the Bracket
Step 1: Remove ½” fixture knockout.
Step 2: Slide to open the Sensor Carrier back cover.
Step 3: Using your thumb or pliers, push and remove the knockout of the front carrier.
Step 4: Insert the ½” Chase Nipple through the knockout hole in the carrier.
Step 5: Insert the sensor into the carrier by pulling the cable through the Chase Nipple. Make sure the sensor lens clicks and is visible through the hole in the front.
Step 6: Slide to close the back cover.
Step 7: Mount the carrier to the fixture by tightening the Chase Nipple with the locknut.
Wiring the Cables to the Control Unit or Driver
Wire the other end of the sensor cable to the Control Unit, driver, or power supply.
Model: CASE-SU-5E
Recommended article
Downloads:
Sensor Cleaning and Maintenance
To keep the Enlighted lighting sensor system working and functioning as it should, learn how to manage and care for your sensors. Dirt on the sensor lens can interfere in its signal detection, so Enlighted recommends regular cleaning and maintenance to head off future problems. The sensors are made with a variety of materials, and only the Ruggedized sensor variant has IP ratings.
The following are general guidelines for the maintenance of sensors.
- Use soap and water during cleaning. An alternative 70% Isopropyl Alcohol (IPA) can be used to clean the sensor. Note: The use of other chemicals such as chlorides, ketones, and degreasers accelerates the aging of the devices and gives them a yellowish color.
- Use only a lint-free and damp soft cloth or paper towel to prevent scratches and brightness degradation. Avoid abrasive paper towels, pads, or similar items.
- Avoid excessive scrubbing, which might cause damage.
- If possible, unplug all external power sources, devices, and cables.
- Keep liquids away from the product.
- Don't get moisture into any openings, especially around areas with the wiring.
- Don't use bleaches or aerosol sprays.
- Don't spray cleaners directly onto the product.