Emergency Lighting Solutions

Emergency lighting solutions exist for fixtures with either Control Units or IoT Ready Profile 0 Drivers. Specification Sheets for all supported devices are found at the bottom of this page. The following emergency lighting solutions are described here.

  1. Emergency Lighting with Control Unit (CU-4E-FMH) 
  2. Emergency Lighting with IoT Ready Profile 0 Drivers
  3. Emergency Lighting with IoT Ready Profile 1 Drivers: Not Supported
  4. Emergency Lighting with DALI Drivers

1. Emergency Lighting with Control Unit (CU-4E-FMH) 

There is NO Emergency version of the CU-4E, so a separate UL924 device is required in all Emergency Fixtures.

Enlighted Available UL924 Devices

We have tested and qualified multiple UL924 devices with the CU-4E.  The table below summarizes the devices that we can supply directly.

Product Code Manufacturer and Part Number Line Diagram Line Diagram

UL924-FD-BSR-120V

Functional Devices ESR2401D

ESR2401D Nipple Mount Relay, 120V only

ESR2401D Nipple Mount Relay, 120V only,
93-02703-02

UL924-FD-BSR-208V-277V

Functional Devices ESR2402D

ESR2402D Nipple Mount Relay, 208-277V only

ESR2402D Nipple Mount Relay, 208-277V only, 93-02702-02

UL924-FD-ESRB

Functional Devices ESRB

NOTE: The ESRLBCND is preferred over the ESRB. Please use ESRLBCND for all new designs.

ESRB Fixture Mount Relay, 120-277

ESRB Fixture Mount Relay, 120-277V,
93-02672-04

Fixture Mount Relay 120-277V with Ecosense Dimming

SU-5 and CU-4 with ESRB and Ecosense for Emergency Line Dimming Control, 93-02845-02

UL924-FD-ESRN

Functional Devices ESRN

ESRN Nipple Mount Relay, 120-277V
93-02692-03

ESRN Nipple Mount Relay 120-277V,
93-02692-03

ESRN Nipple Mount Relay 120-277V  for Pendant Lighting Application
93-02946-01

ESRN Nipple Mount for Pendant Lighting Application, 93-02946-01

UL924-ESRLBCND

Functional Devices ESRLBCND

NOTE: The ESRLBCND is preferred over the ESRB. Please use ESRLBCND for all new designs.

ESRLBCND Fixture Mount Zero Delay Relay, 120-277V
93-03166-02

UL924 ESRLBCND Device with Control Unit (03166-02)

Other UL924 Devices

Supported but not stocked by Enlighted.  These devices must be ordered directly from the manufacturer or via distribution.
 
Manufacturer and Part Number Line Diagram Line Diagram

LVS RRU-X-UNV

RRU-X-UNV Fixture Mount Shunt Relay

RRU-X-UNV Fixture Mount Shunt Relay, 93-02673-01

EPC-1-D-HV 

Profile 0, 0-10V Driver, with SU-5 IoT Ready UL924 347 VAC

Profile 0, 0-10V Driver, with SU-5 IoT Ready UL924 347 VAC (03136-02)

2. Emergency Lighting with IoT Ready Profile 0 Drivers

Profile 0 drivers are 0-10V analog dimming drivers with an auxiliary DC voltage output that powers the sensor directly.  No control unit is used with Profile 0 Drivers.

In the Emergency condition, the 0-10V dimming signal must be disconnected so the fixture will come on at full intensity.   This allows a different set of UL924 devices to be used.

Enlighted Available UL924 Devices

Product Code Manufacturer and Part Number Description Line Diagram
UL924-FD-BSR-120V Functional Devices ESR2401D Nipple Mount Relay, 120V only Profile 0, 0-10V Driver with SU-5 IoT Ready UL924, 93-02766-04
UL924-FD-BSR-208V-277V Functional Devices ESR2402D Nipple Mount Relay, 208-277V only Same as above

Other UL924 Devices

Supported but not stocked by Enlighted.  These devices must be ordered directly from the manufacturer or via distribution.

Manufacturer and Part Number Description Line Diagram
Functional Devices ESR01P Nipple Mount Relay, 120V only Profile 0, 0-10V Driver with SU-5 IoT Ready UL924, 93-02766-04
Functional Devices ESR02P Nipple Mount Relay, 208-277V only Same as above

3. Emergency Lighting with IoT Ready Profile 1 Drivers

Not supported. Use Control Unit or Profile 0 alternatives for Emergency Lighting. 

4. Emergency Lighting with DALI Drivers

Emergency lighting with DALI drivers is handled differently in North America (NA) vs other regions of the world.  In NA, a bypass switching device often referred to as a UL924 device, is used to disable or bypass the lighting controls.  In other regions, a special DALI device type, Device Type 1 (DT1), defined in part 202 of the DALI standard (EN62386-202) is typically used. Enlighted supports both approaches as detailed in the sections below.

UL924 Device Specifications

Functional Devices

https://www.functionaldevices.com/products/lighting-controls/ul924-emergency-relays/

Data Sheets for the following devices can be found below :

  • ESRB and ESRNSpecification Sheet for ESRB (fixture mount) and ESRN (nipple mount) devices 
  • ESR2401D - Specification Sheet (120VAC )
  • ESR2402D - Specification Sheet (208-277VAC)
  • ESR01P - Specification Sheet (120VAC)
  • ESR02P - Specification Sheet (208-277VAC)
  • ESRLBCND - Specification Sheet (120-277VAC)

LVS

http://www.lvscontrols.com/rru-x-unv.php

 

Downloads:

Canadian Emergency Lighting

For Canadian installations where the mains voltage is frequently 347 VAC, the emergency lighting solutions available for these types of fixtures require either IoT Ready Profile 0 (Dim to off) Drivers or 0-10VDC Dimming Drivers with SR Bridge. 

Emergency Lighting with 347VAC IoT Ready Profile 0 Drivers

Profile 0 drivers are 0-10V analog dimming drivers with an auxiliary DC voltage output that powers the sensor directly.  No control unit is used with Profile 0 Drivers. In the Emergency condition, the 0-10V dimming wires connected to the UL924 device will allow the fixture to come on at full intensity. 

Emergency Lighting with 347VAC 0-10VDC Dimming Drivers with SR Bridge

0-10VDC Dimming Drivers use the Signify Sensor Ready (SR) Bridge to allow the Enlighted 2-wire sensor to control fixtures with 347VAC drivers. In the Emergency condition, the 0-10 dimming wires connected to the UL924 device will allow the fixture to come on at full intensity.

The UL924 Devices listed below are supported but not stocked by Enlighted. These devices must be ordered directly from the manufacturer or via distributor.

Manufacturer and Part Number Description Line Diagram
LVS UL924 EPC-1-D-HV, LVS LVS Emergency power, 347V only Profile 0 (Dim-to-Off) Driver Profile 0, 0-10V Driver, with SU-5 IoT Ready UL924 347 VAC (03136-02)
LVS UL924 EPC-1-D-HV, LVS LVS Emergency power, 347V only 0-10VDC Drivers, with SR Bridge SU-5, 2-wire Sensor with Profile 0 Drivers, SR Bridge, and UL924 Device, 347 VAC (03181-02)

Other UL924 Devices

This Line Diagram given in the following table is for LVS UL924 device and 120-277VAC application.

Manufacturer and Part Number Description Line Diagram

LVS RRU-X-UNV

RRU-X-UNV Fixture Mount Shunt Relay

RRU-X-UNV Fixture Mount Shunt Relay, 93-02673-01

 

Recommended articles:

Canadian Wiring 347 VAC Solutions

For Canadian installations where the mains voltage is frequently 347 VAC, which is beyond the limits of the Enlighted Control Unit (CU-4E), Enlighted suggests the following 347 VAC drivers that are compatible with the 2-wire SU-5 sensors when used in conjunction with an XSR Bridge. The following list of DALI drivers and 0-10V drivers can be used directly with the Enlighted 2-wire sensors with an XSR Bridge.

DALI Drivers with Built-in Power Supply Unit and Power Metering Function

When you select one of the following listed drivers, the driver provides sensor powering and supports the DALI Power Metering function directly.

Manufacturer Model Number Certifications       Power Rating (W)

Input Voltage Range

(VAC/DC) 

Output Current

(mA)  

Output Voltage Range

(VDC)

Dimming Type                                                              

PSU in the Driver

(Yes/No)

Power metering function

(Yes/No) 

Philips/Signify XJ180C090V285VSF2M UL ETL CSA D4i 180 277 - 480 100 - 900 100 - 285 DALI Log 10 - 100% and DALI Linear 10 - 100% Yes Yes
Philips/Signify XJ180C125V210VSF2M UL ETL CSA D4i 180 277 - 480 100 - 1250 70 - 210 DALI Log 10 - 100% and DALI Linear 10 - 100% Yes Yes
Philips/Signify XJ180C180V144VSF2M UL ETL CSA D4i 180 277 - 480 100 - 1800 50 - 144 DALI Log 10 - 100% and DALI Linear 10 - 100% Yes Yes

DALI Drivers without Power Supply Unit or Power Metering Function

When you select one of the following listed drivers, an External DALI PSU is required.  To set up Soft Metering, the fixture manufacturer must provide the power consumption vs dimming setting.

Manufacturer Model Number         Certifications Power Rating (W)

Input Voltage Range

(VAC/DC)

Output Current

(mA)                            

Output Voltage Range

(VDC)

Dimming Type

PSU in the Driver

(Yes/No)

Power metering function

(Yes/No)

ULT D700C30347D-C  UL 30 347 VAC 700 15 - 44 DALI 1% No No
ULT D10CC30347D-C  UL 30 347 VAC 1050 15 - 44 DALI 1% No No
ULT D10CC55347D-C  UL 55 347 VAC 1050 11 - 29 DALI 1% No No
ULT D15CC55347D-C  UL 55 347 VAC 1500 15 - 37 DALI 1% No No
ULT D21CC80347D-D UL 80 347 VAC 2100 11 - 38 DALI 1% No No
ULT D10CC55347D-K/KS UL 55 347 VAC 1050 11 - 29 DALI 1% No No
ULT D15CC55347D-K/KS UL 55 347 VAC 1500 15 - 37 DALI 1% No No
                   

0-10V Profile 0 Dimming LED Drivers

The list of 0-10V drivers is available at different power levels from 20 to 95 watts to meet various luminaire size requirements. You can use multiple drivers with a single 2-wire sensor and the XSR-Bridge.

Manufacturer             Model Number                                                  Certifications Power Rating (W) Input Voltage Range (VAC) Output Current (mA)                                Output Voltage Range (VDC)               Dimming Type
Osram OTi 30/347/1A0 DIM L AUX UL 30 347 350 - 1050 10 - 55 0 - 10V 10%
Osram OTi 48/347/2A0 DIM L AUX UL 48 347 700 - 2000 10 - 55 0 - 10V 10%
Osram OTi 48/347/2A0 DIM-1 L AUX UL 48 347 700 - 2000 10 - 55 0 - 10V 1%
Osram OTi 50/347/1A4 DIM L AUX UL 50 347 400 - 1400 10 - 55 0 - 10V 10%
Osram OTi 85/347-480/2A3 DIM-1LHB AUX UL 85 347 - 480 700 -2300 10 - 55 0 - 10V 10%
Osram OTi 85/347-480/2A3 DIM-1 L AUX UL 85 347-480 700 - 2300 10 - 55 0 - 10V 10%
Osram OTi 95W/UNV/2750C/2DIM+/P6/AUX UL 95 347-480 700 - 2750 15 - 54 0 - 10V 1%
               

This solution with the XSR bridge is only for 2-wire sensors; the 2-wire sensor connects to the XSR bridge. See the line diagram SU-5 (2-wire) with XSR Bridge and (347v) 0-10v Driver (03066-02), which is the most preferred solution.  

An alternative method, when energy metering is not required, uses a 347 VAC Profile 0 driver with an 8-pin sensor and adapter cable. In this case, the sensor is powered from the Auxiliary DC supply of the driver. Refer to the following line diagrams: