This diagram shows a fixture with both emergency and normal segments being controlled via a single sensor, a single Control Unit (CU), and a single UL924 device.
Please note that the Control Unit's (CU) Load Limit, NEMA 410 Rating and 0-10 VDC Source/Sink limits cannot be exceeded when installing multiple drivers on a single Sensor/CU. CU Load limit is 5A, NEMA 410 rating for Peak Inrush current is 320A and the Source/Sink limit of the 0-10VDC Control wires is +/- 10mA.