Download the Manage Riser diagram for Gen 5, SU-5, 2-wire sensors.
This article shows the placement of Enlighted Gen 5, SU-5, 2-wire sensors with control units, gateways, switches, and Manage.
- Enlighted devices and wiring must be installed per state, local, and National Electric Codes.
- The maximum CAT5e or CAT6 cable distance between Gateway and PoE switch or PoE switch to PoE switch is 300' and installation is as per IEEE 802.3 Standards.
- One dedicated 20A, 120v circuit with the duplex receptacle, recommended for each 8-port PoE switch and Enterprise Manage.
- Fixtures with integrated Enlighted sensors and control units communicate wirelessly with the Enlighted Gateway.
- Groups of fixtures controlled by an Enlighted (2-wire) sensor unit and communicate wirelessly with the Enlighted gateway.
- Enlighted Room Controllers (Wall Switch - WS-2-00) communicate wirelessly with Enlighted sensors on the same radio channel (gateway).
- Enlighted devices and wiring must be installed in accordance with state, local, and National Electric Codes.
- Plug Load Controller communicates wirelessly with the Enlighted Gateway.
Sample devices for the numerical markings in the above riser diagram are listed below:
No | Sample Device |
1 | Sample DALI Downlight group with external PSU |
2 | Sample Troffer with internal PSU SR driver and field mounted external sensor |
3 | Sample Emergency Troffer with internal PSU SR driver |
4 | Sample Troffer with internal PSU SR driver and OEM mounted internal sensor |
5 | Sample Plug Load Controller - ceiling mounted |
6 | Sample Linear Pendant with internal PSU SR driver and OEM mounted internal sensor |
7 | Sample Emergency Linear Pendant with internal PSU SR driver and OEM mounted internal sensor |