Manage Riser Diagram for 2-wire Sensors (03193-03)

Download the Manage Riser diagram for Gen 5, SU-5, 2-wire sensors.

This article shows the placement of Enlighted Gen 5, SU-5, 2-wire sensors with control units, gateways, switches, and Manage.

  • Enlighted devices and wiring must be installed per state, local, and National Electric Codes.
  • The maximum CAT5e or CAT6 cable distance between Gateway and PoE switch or PoE switch to PoE switch is 300' and installation is as per IEEE 802.3 Standards.
  • One dedicated 20A, 120v circuit with the duplex receptacle, recommended for each 8-port PoE switch and Enterprise Manage.
  • Fixtures with integrated Enlighted sensors and control units communicate wirelessly with the Enlighted Gateway.
  • Groups of fixtures controlled by an Enlighted (2-wire) sensor unit and communicate wirelessly with the Enlighted gateway.
  • Enlighted Room Controllers (Wall Switch - WS-2-00) communicate wirelessly with Enlighted sensors on the same radio channel (gateway).
  • Enlighted devices and wiring must be installed in accordance with state, local, and National Electric Codes.
  • Plug Load Controller communicates wirelessly with the Enlighted Gateway.

03193-03.png

Sample devices for the numerical markings in the above riser diagram are listed below:

No  Sample Device
1 Sample DALI Downlight group with external PSU
2 Sample Troffer with internal PSU SR driver and field mounted external sensor
3 Sample Emergency Troffer with internal PSU SR driver
4 Sample Troffer with internal PSU SR driver and OEM mounted internal sensor
5 Sample Plug Load Controller - ceiling mounted
6 Sample Linear Pendant with internal PSU SR driver and OEM mounted internal sensor
7 Sample Emergency Linear Pendant with internal PSU SR driver and OEM mounted internal sensor