Manage Riser Diagram (03168-03)

Download the Manage Riser diagram.

The following detailed riser diagram shows the placement of Enlighted lighting devices such as sensors, control units, gateways, ERC switches, and Manage.

  • Enlighted devices and wiring must be installed per state, local, and National Electric Codes.
  • The maximum CAT5e or CAT6 cable distance between the Gateway and PoE switch or PoE switch to PoE switch is 300'.  Installation is as per IEEE 802.3 Standards.
  • One dedicated 20A, 120v circuit with a duplex receptacle, recommended for each 8-port PoE switch and Enterprise Manage (EEM).
  • Fixtures with integrated Enlighted sensors and Control Units communicate wirelessly with the Enlighted Gateway.
  • Groups of fixtures controlled by an Enlighted sensor and a single Control Unit communicate wirelessly with the Enlighted Gateway.
  • Enlighted Room Controllers (ERCs) communicate wirelessly with Enlighted sensors on the same radio channel (Gateway).