Canadian Wiring 347 VAC Solutions

For Canadian installations where the mains voltage is frequently 347 VAC, which is beyond the limits of the Enlighted Control Unit (CU-4E), Enlighted suggests the following 347 VAC drivers that are compatible with the 2-wire SU-5 sensors when used in conjunction with an XSR Bridge. The following list of DALI drivers and 0-10V drivers can be used directly with the Enlighted 2-wire sensors with an XSR Bridge.

DALI Drivers with Built-in Power Supply Unit and Power Metering Function

When you select one of the following listed drivers, the driver provides sensor powering and supports the DALI Power Metering function directly.

Manufacturer Model Number Certifications       Power Rating (W)

Input Voltage Range

(VAC/DC) 

Output Current

(mA)  

Output Voltage Range

(VDC)

Dimming Type                                                              

PSU in the Driver

(Yes/No)

Power metering function

(Yes/No) 

Philips/Signify XJ180C090V285VSF2M UL ETL CSA D4i 180 277 - 480 100 - 900 100 - 285 DALI Log 10 - 100% and DALI Linear 10 - 100% Yes Yes
Philips/Signify XJ180C125V210VSF2M UL ETL CSA D4i 180 277 - 480 100 - 1250 70 - 210 DALI Log 10 - 100% and DALI Linear 10 - 100% Yes Yes
Philips/Signify XJ180C180V144VSF2M UL ETL CSA D4i 180 277 - 480 100 - 1800 50 - 144 DALI Log 10 - 100% and DALI Linear 10 - 100% Yes Yes

DALI Drivers without Power Supply Unit or Power Metering Function

When you select one of the following listed drivers, an External DALI PSU is required.  To set up Soft Metering, the fixture manufacturer must provide the power consumption vs dimming setting.

Manufacturer Model Number         Certifications Power Rating (W)

Input Voltage Range

(VAC/DC)

Output Current

(mA)                            

Output Voltage Range

(VDC)

Dimming Type

PSU in the Driver

(Yes/No)

Power metering function

(Yes/No)

ULT D700C30347D-C  UL 30 347 VAC 700 15 - 44 DALI 1% No No
ULT D10CC30347D-C  UL 30 347 VAC 1050 15 - 44 DALI 1% No No
ULT D10CC55347D-C  UL 55 347 VAC 1050 11 - 29 DALI 1% No No
ULT D15CC55347D-C  UL 55 347 VAC 1500 15 - 37 DALI 1% No No
ULT D21CC80347D-D UL 80 347 VAC 2100 11 - 38 DALI 1% No No
ULT D10CC55347D-K/KS UL 55 347 VAC 1050 11 - 29 DALI 1% No No
ULT D15CC55347D-K/KS UL 55 347 VAC 1500 15 - 37 DALI 1% No No
                   

0-10V Profile 0 Dimming LED Drivers

The list of 0-10V drivers is available at different power levels from 20 to 95 watts to meet various luminaire size requirements. You can use multiple drivers with a single 2-wire sensor and the XSR-Bridge.

Manufacturer             Model Number                                                  Certifications Power Rating (W) Input Voltage Range (VAC) Output Current (mA)                                Output Voltage Range (VDC)               Dimming Type
Osram OTi 30/347/1A0 DIM L AUX UL 30 347 350 - 1050 10 - 55 0 - 10V 10%
Osram OTi 48/347/2A0 DIM L AUX UL 48 347 700 - 2000 10 - 55 0 - 10V 10%
Osram OTi 48/347/2A0 DIM-1 L AUX UL 48 347 700 - 2000 10 - 55 0 - 10V 1%
Osram OTi 50/347/1A4 DIM L AUX UL 50 347 400 - 1400 10 - 55 0 - 10V 10%
Osram OTi 85/347-480/2A3 DIM-1LHB AUX UL 85 347 - 480 700 -2300 10 - 55 0 - 10V 10%
Osram OTi 85/347-480/2A3 DIM-1 L AUX UL 85 347-480 700 - 2300 10 - 55 0 - 10V 10%
Osram OTi 95W/UNV/2750C/2DIM+/P6/AUX UL 95 347-480 700 - 2750 15 - 54 0 - 10V 1%
               

This solution with the XSR bridge is only for 2-wire sensors; the 2-wire sensor connects to the XSR bridge. See the line diagram SU-5 (2-wire) with XSR Bridge and (347v) 0-10v Driver (03066-02), which is the most preferred solution.  

An alternative method, when energy metering is not required, uses a 347 VAC Profile 0 driver with an 8-pin sensor and adapter cable. In this case, the sensor is powered from the Auxiliary DC supply of the driver. Refer to the following line diagrams:

Recommended article:

Was this article helpful?
0 out of 0 found this helpful
Have more questions? Submit a request

Comments