High Bay Sensor, 2-wire, (SU-5S-2W-H)

Download the Highbay Sensor, 2- wire, Installation Guide PDF: English rev.05 | German rev.05 | French rev.05

Overview

The High Bay Sensor, 2-wire, is a complete sensing and lighting control node powered from its attached light fixture. Sensor information combined with a configurable behavior profile makes the High Bay Sensor, 2-wire, an integral component of intelligent lighting control and sensing solution. With integrated wireless communications for data transmission and remote configuration as well as autonomous fixture-level control, this sensor brings advanced lighting automation to a whole new level.

2-Wire_Surface_Mount_Cover_02.png

Installation

Shipped Components

Supplemental Components

  • Adjustable Mounting Bracket: BRKT-SU

Tools you may Need

  • Wire Stripper

Caution

A qualified electrician must perform installation and maintenance under local, state, and national electrical codes (NEC) and requirements.

Surface Mount Sensor Installation

The High Bay Sensor, 2-wire, can be mounted to ceiling tiles using an anchor screw or pendant and industrial fixtures using the adjustable mounting bracket. 

Step 1: De-energize the luminaire.

Mounting using an Anchor Screw

The High Bay Sensor, 2-wire, should be mounted to the ceiling tile within a few inches (between 13/4” to 3”) of the lighting fixture.

Step 2: Determine the location of the sensor. Push and rotate the anchor screw to the tile at that location. 

Picture1.jpg

Step 3: See section Connecting the Sensor Cable to the LED Driver before proceeding further.

Step 4: Select a place near the anchor screw for the pair of wires from the LED driver to exit. Make a small cut in the ceiling tile for the wire to exit. 

Step_2_Surface_Mount.png

Step 5: Connect the other end of the wires to the bottom of the sensor.

Picture_3.PNG

Step 6: Align the anchor screw with the slot provided on the sensor bottom. Slide the sensor onto the screw head.

Picture4.png

Step 7: Slip the excess sensor wire into the plenum area and adjust the ceiling tile to the original position.

Step 8: Energize the luminaire and confirm that the green LED is solid.

Mounting using Adjustable Mounting Bracket

The sensor can be mounted to the pendant and industrial fixtures using the mounting bracket.

Step 1: Determine the mounting location of the sensor on the fixture. To ensure that the fixture does not obstruct the sensor's view, level the sensor to the fixture's bottom and provide enough clearance from the fixture. See the examples below.

Picture5.PNG

Step 2: Bend the adjustable mounting bracket to the required shape. Fasten the bracket to the fixture using two 8” screws.

Picture6.png

Step 3: See section Connecting the Sensor Cable to the LED Driver before proceeding further.

Step 4: Connect the other end of the pair of wires from the LED driver to the bottom of the sensor.

Picture7.PNG

Step 5: Slide the sensor onto the head of the mounting bracket.

Picture9.PNG

Step 6: Secure the sensor cable to the bracket or fixture using cable ties, electrical tape, clips, etc., as appropriate for the installation.

Step 7: Energize the luminaire and confirm that the green LED is solid.

Connecting the Cable to the LED Driver

Step 1: Measure the distance between the sensor’s installation location and the LED driver.

Step 2: Cut two lengths of 18 AWG solid wire of the required length. Strip each end of the two wires leaving 3/8 inch of exposed wire.

Step 3: Connect the end of the pair of wires to the LED Driver.

Picture4.png

LED Description

LED Status Description/Solution
LED not on Power issue or faulty sensor. Check power and wiring.
Blinking Green The commissioned sensor has powered up and has detected motion. If there is no motion in the sensor’s field of view, the blinking will stop. Wave your hands below the sensor to restart LED blinking.
Solid Green The un-commissioned sensor has powered up successfully and passed the wiring test –waiting for discovery.
Blinking Red The un-commissioned sensor has powered up and detected a wiring test issue. Check the wiring.
Solid Red Faulty sensor –replace the sensor.
Solid Blue The sensor received a request to identify itself.
Blinking Blue

The un-commissioned sensor was not able to detect an energy measurement device (Control Unit or Driver).

 

Product Compliance

mceclip0.png mceclip1.png mceclip2.png mceclip3.png mceclip4.png mceclip5.png

Model No:
SU-5S-2W-H: High Bay Sensor, 2-wire
Product Code: SU-5S-2W-H-xxx/SU-5S-2W-H-xxx-FL
xxx: IoT Node (IoT), Connected Lighting (CL),
Independent Lighting/Enlighted One (IL)
FL: Fixtureless
FCC ID: AQQ-SU5S
IC: 10138A-SU5S
Rev.05
DoC: enlightedinc.com/eu-docs/mceclip0.png