ESRN Nipple Mount Relay 120-277V (02692-07)

The line diagram shows the connections between ESRN UL924 with Enlighted Control Unit (CU-4E). 

Please note that the Control Unit's (CU) Load Limit, NEMA 410 Rating and 0-10 VDC Source/Sink limits cannot be exceeded when installing multiple drivers on a single Sensor/CU. CU Load limit is 5A, NEMA 410 rating for Peak Inrush current is 320A, and the Source/Sink limit of the 0-10VDC Control wires is +/- 10mA.

Download the line diagram PDF.

Line_Diagram_-_FD_-_ESRN_-_UL924_w-CU4E-FMH_-_93-02692-07.jpg