Emergency lighting solutions exist for fixtures with either Control Units or IoT Ready Profile 0 Drivers. Specification Sheets for all supported devices are found at the bottom of this page. The following emergency lighting solutions are described here.
- Emergency Lighting with Control Unit (CU-4E-FMH)
- Emergency Lighting with IoT Ready Profile 0 Drivers
- Emergency Lighting with IoT Ready Profile 1 Drivers: Not Supported
- Emergency Lighting with DALI Drivers
1. Emergency Lighting with Control Unit (CU-4E-FMH)
There is NO Emergency version of the CU-4E, so a separate UL924 device is required in all Emergency Fixtures.
Enlighted Available UL924 Devices
We have tested and qualified multiple UL924 devices with the CU-4E. The table below summarizes the devices that we can supply directly.
Product Code | Manufacturer and Part Number | Line Diagram | Line Diagram |
---|---|---|---|
UL924-FD-BSR-120V |
Functional Devices ESR2401D |
ESR2401D Nipple Mount Relay, 120V only |
|
UL924-FD-BSR-208V-277V |
Functional Devices ESR2402D |
ESR2402D Nipple Mount Relay, 208-277V only |
|
UL924-FD-ESRB |
Functional Devices ESRB NOTE: The ESRLBCND is preferred over the ESRB. Please use ESRLBCND for all new designs. |
ESRB Fixture Mount Relay, 120-277 |
|
Fixture Mount Relay 120-277V with Ecosense Dimming |
SU-5 and CU-4 with ESRB and Ecosense for Emergency Line Dimming Control, 93-02845-02 |
||
UL924-FD-ESRN |
Functional Devices ESRN |
ESRN Nipple Mount Relay, 120-277V |
|
ESRN Nipple Mount Relay 120-277V for Pendant Lighting Application |
ESRN Nipple Mount for Pendant Lighting Application, 93-02946-01 |
||
UL924-ESRLBCND |
Functional Devices ESRLBCND NOTE: The ESRLBCND is preferred over the ESRB. Please use ESRLBCND for all new designs. |
ESRLBCND Fixture Mount Zero Delay Relay, 120-277V |
UL924 ESRLBCND Device with Control Unit (03166-02) |
Other UL924 Devices
Manufacturer and Part Number | Line Diagram | Line Diagram |
---|---|---|
LVS RRU-X-UNV |
RRU-X-UNV Fixture Mount Shunt Relay |
|
EPC-1-D-HV |
Profile 0, 0-10V Driver, with SU-5 IoT Ready UL924 347 VAC |
Profile 0, 0-10V Driver, with SU-5 IoT Ready UL924 347 VAC (03136-02) |
2. Emergency Lighting with IoT Ready Profile 0 Drivers
Profile 0 drivers are 0-10V analog dimming drivers with an auxiliary DC voltage output that powers the sensor directly. No control unit is used with Profile 0 Drivers.
In the Emergency condition, the 0-10V dimming signal must be disconnected so the fixture will come on at full intensity. This allows a different set of UL924 devices to be used.
Enlighted Available UL924 Devices
Product Code | Manufacturer and Part Number | Description | Line Diagram |
---|---|---|---|
UL924-FD-BSR-120V | Functional Devices ESR2401D | Nipple Mount Relay, 120V only | Profile 0, 0-10V Driver with SU-5 IoT Ready UL924, 93-02766-04 |
UL924-FD-BSR-208V-277V | Functional Devices ESR2402D | Nipple Mount Relay, 208-277V only | Same as above |
Other UL924 Devices
Supported but not stocked by Enlighted. These devices must be ordered directly from the manufacturer or via distribution.
Manufacturer and Part Number | Description | Line Diagram |
---|---|---|
Functional Devices ESR01P | Nipple Mount Relay, 120V only | Profile 0, 0-10V Driver with SU-5 IoT Ready UL924, 93-02766-04 |
Functional Devices ESR02P | Nipple Mount Relay, 208-277V only | Same as above |
3. Emergency Lighting with IoT Ready Profile 1 Drivers
Not supported. Use Control Unit or Profile 0 alternatives for Emergency Lighting.
4. Emergency Lighting with DALI Drivers
Emergency lighting with DALI drivers is handled differently in North America (NA) vs other regions of the world. In NA, a bypass switching device often referred to as a UL924 device, is used to disable or bypass the lighting controls. In other regions, a special DALI device type, Device Type 1 (DT1), defined in part 202 of the DALI standard (EN62386-202) is typically used. Enlighted supports both approaches as detailed in the sections below.
- For North America applications, see the line diagram showing the connections between an Enlighted SU-5, 2-wire sensor with UL924 SPST device, 2-wire driver, and an internal Power Supply Unit (PSU): UL924 Generic SPST, 2-wire with a Normal and Emergency Driver with Internal PSU (03131-06)
- For non-North American applications a single DALI Type 1 emergency driver can be connected to a sensor. This is illustrated in SU-5 2-wire with DALI Drivers and External PSU with Emergency EU 03381-01 and SU-5 2-wire with SR Driver and LED with Emergency EU-03380-01.
The status of the emergency driver can be tested by use of the DALI Emergency APIs. Since only a single emergency driver is connected to a sensor, the location of any failing emergency driver is immediately identifiable in the system.
UL924 Device Specifications
Functional Devices
https://www.functionaldevices.com/products/lighting-controls/ul924-emergency-relays/
Data Sheets for the following devices can be found below :
- ESRB and ESRN - Specification Sheet for ESRB (fixture mount) and ESRN (nipple mount) devices
- ESR2401D - Specification Sheet (120VAC )
- ESR2402D - Specification Sheet (208-277VAC)
- ESR01P - Specification Sheet (120VAC)
- ESR02P - Specification Sheet (208-277VAC)
- ESRLBCND - Specification Sheet (120-277VAC)
LVS
http://www.lvscontrols.com/rru-x-unv.php
- RRU-X-UNV - Specification Sheet: